AVENTICS | DeviceNet | R499050019–BDL–001–AD
7.7
System stop
The "system stop" mode on the bus coupler is displayed when
both the RUN and MNS LEDs flash quickly.
If the system is stopped, the outputs return to a safe mode
(= "0") and the bus traffic to the DeviceNet master is interrupted.
The system stop mode can only be exited by restarting the
assembly (power on).
If the system stop is activated, this is because of a one-time
error caused by the hardware or firmware.
When starting the bus coupler (power on), the hardware
components are tested. If an error is found, the system is then
set to the "system stop" mode.
Plausibility tests are constantly carried out while the firmware
is running. If an error is detected during these tests, the "system
stop" mode is activated.
7.7.1
Exiting system stop
O
Restart the assembly with "power on".
8
Disassembly and Exchange
You can either exchange the bus coupler or connect additional
input/output modules as needed.
The AVENTICS warranty only applies to the delivered
configuration and extensions taken into account in the
configuration. The warranty no longer applies after a
conversion that exceeds these extensions.
A bus coupler with 32 outputs can only be connected to a VS
that has been designed for 32 valve solenoids.