Residence Condens KIS n
Adjustments table
Table of adjustments for Residence Condens 25 KIS n
Maximum number of fan
Pipes Ø 60
rotations
maximum
(rpm)
length
DHW
CH
4.700
3.900
4.800
4.000
4.900
4.100
5.000
4.200
5.100
4.300
31 (*)
5.200
4.400
5.300
4.500
5.400
4.600
5.500
4.700
5.600
4.800
5.700
4.900
5.800
5.000
5.900
5.100
6.000
5.200
6.100
5.300
6.200
5.400
6.300
5.500
(*) Length that can be installed with pipes in class P1
Table of adjustments for Residence Condens 30 KIS n
Maximum number of
Pipes Ø 60
fan rotations
maximum
(rpm)
length
DHW
CH
5.600
4.700
14
5.700
4.800
19
5.800
4.900
21 (*)
5.900
5.000
6.000
5.100
6.100
5.200
6.200
5.300
6.300
5.400
(*) Length that can be installed with pipes in class P1
The configurations Ø 60 show test data verified in the laboratory.
In the case of installations that differ from those indicated in the
"standard configuration" and "adjustments" tables, refer to the equiv-
alent linear lengths Ø 80 - Ø 60 below.
In any case, the maximum lengths declared in the booklet are
guaranteed, and it is essential not to exceed them.
Component Ø 60
Linear equivalent in metres Ø80 (m)
Bend 45° Ø 60
Bend 90° Ø 60
Extension 0.5m Ø 60
Extension 1.0m Ø 60
Extension 2.0m Ø 60
3.11 Installation of collective positive pressure smoke
pipes
The collective smoke pipe is a flue gases system suitable for col-
lecting and expelling combustion products of several appliances in-
stalled on different floors of a building (fig. 26).
The collective positive pressure smoke pipes can only be used for
type C condensing appliances. Consequently, configuration B53P/
B23P is prohibited.
The installation of the boiler on collective pressure smoke pipes is
only allowed at G20, for all models, adopting a specific check valve,
available as an accessory, to which to refer to for the assembly pro-
cess.
8
ΔP at boiler
Pipes Ø 80
maximum
output with
length
max. length
m
m
11
58
16
90
22
121
28
152
172 (*)
229
271
315
354
390
426
468
519
561
600
639
701
ΔP at boiler
Pipes Ø 80
output with
maximum length
max. length
m
m
75
104
117 (*)
159
190
217
253
301
5
8
2.5
5.5
12
The boiler is dimensioned to function properly up to a maximum pres-
sure inside the smoke pipe not greater than the value indicated in the
"Technical data" table.
Once the check valve has been fitted (fig. 27), proceed with the r.p.m.
adjustment of the fan as shown in paragraph "Adjustments".
Make sure that the air suction and combustion fumes discharge
Pa
pipes are sealed.
90
The installation of the check valve requires the application of the
CAUTION label, supplied with the accessory, on a visible part of the
120
boiler casing. The application of the label is essential for safety pur-
150
poses during the maintenance or replacement of the boiler and/or
180
collective smoke pipes.
200
255
WARNINGS
295
The manufacturer assumes no liability if the check valve and
338
related label is not installed before the commissioning of the
375
boiler.
410
Appliances connected to a collective smoke pipe must all be of
445
the same type and have equivalent combustion characteristics.
485
The number of appliances that can be connected to a collective
535
positive pressure smoke pipe is defined by the designer of the
575
smoke stack.
613
650
MAINTENANCE FOR APPLICATION IN A COLLECTIVE
710
PRESSURIZED SMOKE PIPE
During the scheduled maintenance of the appliance, control also
the efficiency of the check valve to ensure the correct operation and
safety of the system. Before proceeding with maintenance, perform
a products of combustion analysis and check the operating condition
of the boiler.
If performing maintenance to the combustion circuit of the
Pa
boiler (flue gas pipes, heat exchanger, condensate trap, burner,
electrode conveyors, fan) it is necessary to ensure the closure
145
of the flue gases pipe coming from the pressurised smoke pipe
183
and check for leaks.
200
Subsequently (fig. 28-29):
- Switch off the electrical supply by turning the system's main switch
255
to "Off".
295
- Close the gas shut-off valve.
330
- Remove the connections cover and the casing.
- Undo the fixing screws of the control panel.
377
- Disconnect the control panel and then rotate it forward.
440
- Disconnect and remove the air distribution box cover.
- After unscrewing the fixing screws, remove the right side of the air
distribution box.
- Unscrew the gas valve train fixing nut to the air distribution box.
- Unscrew and remove the mixer connection gas train (A).
- Remove the electrical connections of the ignition electrodes and
flame detection and the electrical connections of the fan.
- Unscrew the 4 screws that fix the air gas conveyor to the main heat
exchanger (B).
- Remove the conveyor-fan assembly (C) from the heat exchanger,
being careful not to damage the burner insulation panel.
- To access the check valve, remove the fan by unscrewing the 4
screws (D) to the conveyor.
- Make sure there are no foreign material deposits on the membrane
of the check valve and if any remove them and checking for dam-
age.
- Check the correct opening and closing operation of the valve
- Reassemble the components in reverse order, making sure the
check valve is put back in the correct direction (see fig. 29)
Failure to comply with the above can lead to the abnormal func-
tioning of the check valve and the consequent diverse perfor-
mance of the boiler until its failure.
Failure to comply with the above may compromise the safety
of people and animals due to the possible leakage of carbon
monoxide from the smoke pipe.