AVENTICS | PROFIBUS DP | R499050016–BDL–001–AE
Technical Data
Electrics
Inputs DIN EN 61131-2
Total current of 24 V sensor supply for all input modules limited to 0.7 A.
Input delay 0 – 1
Input delay 1 – 0
Line length for
M8 and M12 connection
Electrics
Outputs DIN EN 61131-2
Output voltage
Output current
Overload protection
Line length for
M8 and M12 connection
Power supply
U
and U
Q1
Q2
Cable length for power supply
10.3 8x input modules, RMV04-8DI_M8 and
RMV04-8DI_M12
10.4 8x output modules, RMV04-8DO_M8 and
RMV04-8DO_M12
For thermal reasons, the outputs may not be loaded
with anything above the nominal current for long periods.
8 digital inputs, type 3,
two-wire proximity switch with a quiescent
current of max. 2.5 mA can be connected
H signal voltage drop 1.5 V
Switches off at 0.6 to 1.2 A
Autom. start-up when load is reduced
3 ms
3 ms
Max. 30 m
8 digital outputs
Nominal value 24 V
Nominal value 0.5 A
Max. 30 m
Nominal value 24 V
(+20 %/-15 %)
Max. 20 m