Herunterladen Diese Seite drucken

Aventics DeviceNet Betriebsanleitung Seite 88

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
88
AVENTICS | DeviceNet | R402003659–BAL–001–AG
Appendix – Bus master configuration
Diagnostic Data Length
Diagnostic status
Diagnostic Data Class 0x65
Instance 0x02 Attribute
Table 29
MSB
Bit
Bit
15
14...2
0
1
Contains the length of the current diagnostic data. With the bus coupler,
the length is:
W
0x00 byte, if diagnosis is not active
W
0x01 byte, if diagnosis is active
W
0x00 No diagnosis is active
W
0x01 Diagnosis is active (group diagnosis flag)
The Diagnostic Data Object can be mapped in the Assembly Object
behind the input data. The Parameter Data Object and the Device
0x6E
Parameter Data object function as a diagnostic filter.
Manufacturer Status Register – Class 0x65, Instance 0x01,
Attribute 0x65
LSB
Default value: 0x0003
Bit
Bit
1
0
Default configuration of the diagnostics
0
Not active
1
Active
Diagnostic data
0
Not mapped in Assembly Object
1
Mapped behind the input data in the Assembly
Object
Reserved
Critical error
No existing critical error
Existing critical error