8. Specifications

MODELS
Capacity (VA)
Capacity (Watts)
INPUT
Nominal Voltage
Voltage Range
Voltage Comeback
Nominal Frequency
Frequency Range
Phase
Power Factor (100% Load)
Harmonic Distortion (THDi; 100% Load)
OUTPUT
Phase
Nominal Voltage
AC Voltage Regulation
(Double-Conversion Mode)
AC Voltage Regulation
(Converter Mode or Battery Mode)
Power Factor
AC Voltage Regulation (ECO Mode)
Frequency
Frequency Regulation
(Converter Mode or Battery Mode)
Frequency Range (Battery Mode)
Overload (AC Mode)
Overload (Battery Mode)
Current Crest Ratio
Harmonic Distortion (100% Load)
Transfer Time (Line ‹—› Battery)
Transfer Time (Inverter ‹—› Bypass)
Transfer Time (Inverter ‹—› ECO)
BYPASS INPUT
Nominal Voltage
Phase
Voltage Range
Nominal Frequency
Frequency Range
Overload (Bypass Mode)
EFFICIENCY
AC Line Mode
ECO Mode
Battery Mode
PARALLEL
Parallel for Capacity
Parallel for Redundancy
INTERNAL BATTERIES (S3M30KX and S3M40KX include internal batteries. Versions are also available without internal
batteries: S3M30KX-NIB and S3M40KX-NIB.)
Type
Capacity
Quantity
Runtime (50% / 100% Load)
Recharge Time
Maximum Charging Current
Float Voltage
Boost Charging
End of Discharge
S3M30KX
S3M40KX
30 kVA
27 kW
Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
Ph-Ph 208-478V at < 50% Load; Ph-Ph 208-478V to 305-478V at 50% to 80% Load
(Voltage Range Varies with Load); Ph-Ph 305-478V at > 80% Load
Low-Loss Voltage +10V; High-Loss Voltage -10V
46-54 Hz (50 Hz System); 56-64 Hz (60 Hz System)
3-Phase with Neutral (3-Phase, Neutral + Ground)
3-Phase with Neutral (3-Phase, Neutral + Ground)
Ph-Ph 380V/400V/415V (Ph-N 220V/230V/240V)
46-54 Hz (50 Hz System); 56-64 Hz (60 Hz System)
50 Hz ± 0,1 Hz or 60 Hz ± 0,1 Hz
Up to 110% = 10 min; Up to 130% = 1 min; > 130% = 1 s
Up to 110% = 30 s; Up to 130% = 10 s; > 130% = 1 s
≤ 2% THD (Linear Load); ≤ 4% THD (Non-Linear Load)
Synchronous = 0 ms; Asynchronous < 4 ms
3-Phase with Neutral (3-Phase, Neutral + Ground)
Selectable: ± 1-4 Hz (Default: ± 4 Hz)
94% at 100% Resistive Load; 93,5% at 50% Resistive Load
98%, at 100% Resistive Load; 97,5% at 50% Resistive Load
93,5% at 100% Resistive Load; 93% at 50% Resistive Load
12V Non-Spillable VRLA AGM/GEL
9 Ah
80 (2 x Strings of 20 + 20)
17/5.7 min
15/5 min
9 h to 90%
2A ± 10%
13,65V/Battery; 2,27V/Cell
14,1V/Battery; 2,35V/Cell
10V/Battery; 1,67V/Cell
37
S3M60KX
40 kVA
60 kVA
36 kW
54 kW
50/60 Hz (Auto-Selectable)
≥ 0,99
< 3%
±1% (Balanced Load)
±1%
0,9
± 11V of Nominal
± 0,1 Hz
3:1 Maximum
0 ms
< 10 ms
Ph-Ph 380V/400V/415V
Upper Limit: Ph-N 231-264V
Lower Limit: Ph-N 176-209V
50/60 Hz (Auto-Selectable)
< 150% = 1 min
Up to 3 Units
N/A
10 Ah
No Internal Batteries
External Batteries Required for
S3M30KX-NIB, S3M40KX-NIB,
S3M60KX, S3M80KX, S3M100KX,
S3M120KX, S3M160KX and S3M200KX
S3M80KX
80 kVA
72 kW