2/2 Schrägsitzventil Typ 582
2/2 Angle Seat valve Typ 582
5.4

Installation

Before installation, ensure that the angle seat valve is suitable for the operating conditions.
These include function, materials, operating pressure und working media in connection with operating
temperature. Depending on the operating conditions and weight of the valve a suitable fixture has to
be applied.
Take also care for aligning pipes.
Clean pipes before installation.
Follow the laws, directives and regulations for welding which are valid in your
Disassemble the valve before welding. See chapter 5.3.2.
Weld in valve body and cool down.
Assemble actuator on valve body, see chapter 5.3.1.

5.4.1. Installation - Butt weld spigots:

Remove the actuator before welding the valve body into the pipeline. Allow the welding nozzles to cool
after welding. Reassemble the valve body and drive.

5.4.2. Installation - Clamp connections:

When assembling clamp connections, insert a gasket between the body clamp and the adjacent piping
clamp and join them using the appropriate clamp fi tting. The gasket and the clamp for clamp
connections are not included in the scope of delivery.

5.4.3. Installation - Threaded connections:

Screw the threaded connections into the piping in accordance with valid standards. Screw the valve
body into the piping, use appropriate thread sealant. The thread sealant is not included in the scope of
delivery.

5.4.4. Installation - Flange connection:

Install the valve in the condition it is delivered in. Pay attention to clean, undamaged sealing surfaces
on the mating flanges. Align flanges carefully before installing them. Centre the seals accurately. Use
all flange holes.
Connect the valve flange and the piping flange using appropriate sealing material and matching
bolting (sealing material and bolts are not included in the scope of the delivery). Tighten the bolts
diagonally! Only use connector elements made of approved materials!
5.5.

Implementation

Ensure correct installation before implementation. Check tightness in clamping area of
actuator and valve body. Also check the valve for function
© 2019 SED Flow Control GmbH, Bad Rappenau