Note
End position
By simultaneously pressing the
3. After checking, move the actuator to a central position. This accelerates the initialization process.
5.7.2

Automatic initialization of part-turn actuators

Condition
The following conditions must be fulfilled before activating the automatic initialization:
1. The actuating range of the actuator can be passed through completely.
2. The actuator shaft is at a central position.
Initializing the positioner automatically
Note
Interrupting initialization
An ongoing initialization can be interrupted at any time. To do this, press the
retained.
All parameters are reset to factory settings only if you have explicitly activated the preset settings in the "PRST" parameter.
1. Switch to the "Configuration" mode. To do this, press the
following:
2. Use the
button to change from linear actuator to part-turn actuator until the display shows the following:
3. Call the "2.YAGL" parameter. To do this, briefly press the
automatically. The display shows the following:
4. Call the "4.INITA" parameter. To do this, briefly press the
SIPART PS2 (6DR5...)
A5E03436620-02, 01/2013
and
buttons, you reach the end position faster.
. The settings configured until then are
button for at least 5 seconds until the display shows the
button. This parameter has already been set to 90°
button. The display shows the following: