Herunterladen Inhalt Inhalt Diese Seite drucken

BFT VIRGO Installations- Und Gebrauchsanleitung Seite 18

Arm automationen fuer flugelgittertire
Vorschau ausblenden Andere Handbücher für VIRGO:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 30
ENGLISH
Refer to Figures A and B for the configuration procedure.
10.1) PARAMETER MENU (PARAm)
-
Automatic Closing Time (TCA) [ 10s ]
Set the numerical value of the automatic closing time from 3 to 60
seconds.
-
Motor 1 torque (m1 t) [ 50% ]
(UNIPRO ⇒ Advanced parameters ⇒ address 3)
Set the numerical value of the motor 1 torque between 1% and 99%.
-
Motor 2 torque (m2 t) [ 50% ]
(UNIPRO ⇒ Advanced parameters ⇒ address 4)
Set the numerical value of the motor 2 torque between 1% and 99%.
-
Motor 1 slow-down torque (m1 t slow) [ 45% ]
(UNIPRO _ Advanced parameters _ address 8)
Set the numerical value for slow-down torque of motor 1 between 1%
and 99%.
-
Motor 2 slow-down torque (m2 t slow) [ 45% ]
(UNIPRO _ Advanced parameters _ address 9)
Set the numerical value for slow-down torque of motor 2 between 1%
and 99%.
NOTES: In case of obstacle detection, the Ampere-stop function stops
the leaf movement, reverses the motion for 1 sec. and then halts in the
STOP status. The motor slow-down torque represents the maximum
torque supplied to the motor during the slow-down phase. It must be set
to a lower value with respect to the motor torque, in order to allow the
Ampere-stop function to be also activated during the slow-down phase.
WARNING: Check that the impact force value measured at
the points established by the EN 12445 standard is lower
than that specified in the EN 12453 standard.
Incorrect sensitivity setting can cause injuries to persons or
animals, or damage to things.
-
Opening delay time (open delay time) [ 1s ]
Set the opening delay time for motor 2 relative to motor 1, between 1
and 10 seconds.
Closing delay time (cls delay time) [ 1s ]
-
Set the closing delay time for motor 1 relative to motor 2, between 1 and
10 seconds.
-
Motor 1 Normal Speed Time (m1 fast time) [ 5s ]
(UNIPRO fi Advanced parameters fi address 6)
Set the time to normal speed (not slowed down), ranging from 1 to 30
seconds.
-
Motor 2 Normal Speed Time (m2 fast time) [ 5s ]
(UNIPRO fi Advanced parameters fi address 7)
Set the time to normal speed (not slowed down), ranging from 1 to 30
seconds.
Note: The slow-down time, on closing and on opening, is obtained by
timing one manoeuvre, and setting a lower value within this parameter.
If, for example, one manoeuvre lasts 25 seconds, set "normal speed
time" to 20s to obtain 5s of slow-down time, both on closing and on
opening.
-
Slow-down speed (slov speed) [ 2 ]
(UNIPRO ⇒ Advanced parameters ⇒ address 5)
Set the slow-down speed by choosing from the following values:
0 – slow-down disabled
1 – slow-down to 50% of normal speed
2 – slow-down to 33% of normal speed.
3 – slow-down to 25% of normal speed.
10.2) LOGIC MENU (logic. )
-
TCA (TCA) [ OFF ]
ON
Activates automatic closing
OFF Excludes automatic closing
-
3 Steps (3 step) [ OFF ]
ON
Enables 3-step logic. A Start impulse has the following effects:
door closed:
opens
on opening:
stops and enters TCA (if configured)
door open:
closes
on closing:
stops and reopens
OFF Enables 4-step logic. A Start impulse has the following effects:
door closed: opens
on opening:
stops and enters TCA (if configured)
door open:
closes
on closing:
stops and does not enter TCA (stop)
after stopping: opens
-
Impulse lock (ibl open) [ OFF ]
ON
The Start impulse has no effect during the opening phase.
OFF The Start impulse becomes effective during the opening or closing
phase.
18 -
VIRGO Ver. 03
INSTALLATION MANUAL
-
Rapid closing (fast cls) [ OFF ]
ON
Closes the gate after photocell disengagement, before waiting for
the end of the TCA set.
OFF Command not entered.
-
Photocells on opening (photc. open) [ OFF ]
ON:
In case of obscuring, this excludes photocell operation on opening.
During the closing phase, it immediately reverses the motion.
OFF:
In case of obscuring, the photocells are active both on opening and
on closing. When a photocell is obscured on closing, it reverses the
motion only after the photocell is disengaged.
Photocell test (test phot) [ OFF ]
-
(UNIPRO ⇒ Advanced logics ⇒ address 14)
ON
Activates photocell check
OFF Deactivates photocell check
If this setting is not activated (OFF), it inhibits the photocell checking
function, allowing connection of devices not provided with additional
checking contact.
-
Gate-open or 2nd radio channel warning light (SCA 2ch) [ OFF ]
ON
The output between terminals 25 and 26 is configured as Gate-open
warning light, in this case the 2nd radio channel controls pedestrian
opening.
OFF The output between terminals 25 and 26 is configured as 2nd radio
channel.
-
Motors in operation (1 mot ON) [ OFF ]
ON
Only motor 2 is in operation (terminals 1 and 2).
With this configuration, the pedestrian input is disabled.
OFF Both motors are in operation.
-
Lock hold (bloc persist) [ OFF ]
ON
To be used when opening and closing mechanical backstops are
fitted.
This function activates leaf pressure on the backstop, without this
being considered as an obstacle by the ampere-stop sensor.
Then the leaf continues its stroke for another 0,5s, after intercepting
the limit switches. Therefore the limit switches are triggered slightly
in advance, and the leaves will stop perfectly on the end stop plate.
OFF To be used when no mechanical backstops are fitted.
Movement is exclusively stopped by the limit switches being triggered;
in this case it is necessary to set the opening and closing limit switch
triggering point with precision.
-
Prealarm (preal) [ OFF ]
ON
The blinker comes on about 3s before the motors start.
OFF The blinker comes on at the same time as the motors start
-
Fixed code (fixed code) [ OFF ]
(UNIPRO ⇒ Advanced logics ⇒ address 13)
ON
The receiver is configured for operation in fixed-code mode, see
paragraph on "Radio Transmitter Cloning".
OFF The receiver is configured for operation in rolling-code mode, see
paragraph on "Radio Transmitter Cloning".
-
Radio transmitter programming (radio prog) [ OFF ]
(UNIPRO ⇒ Advanced logics ⇒ address 15)
ON
This enables transmitter storage via radio:
1 – First press the hidden key (P1) and then the normal key (T1, T2,
T3 or T4) of a transmitter already memorised in standard mode by
means of the radio menu.
2 – Within 10s press the hidden key (P1) and the normal key (T1, T2,
T3 or T4) of a transmitter to be memorised.
The receiver exits the programming mode after 10s, other new
transmitters can be entered before the end of this time.
This mode does not require access to the control panel.
OFF This disables transmitter storage via radio.
The transmitters can only be memorised using the appropriate Radio
menu.
10.3) RADIO MENU (RADIO)
-
Add
Allows you to add one key of a radio control device to the receiver memory;
after storage it displays a message showing the receiver number in the
memory location (from 01 to 64).
Add Start button (add start)
associates the required key to Start command
Add 2ch button (add 2ch)
associates the required key to 2nd radio channel
-
Read (read)
Checks one key of a receiver; if stored it displays a message showing
the receiver number in the memory location (from 01 to 64), and the key
number (T1, T2, T3 or T4).
-
Eliminate list (erease 64)
WARNING! Completely removes all memorised radio control devices

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis