Appendix A
A.1 I/O Connections and Wiring
Note
Relays shown in Power OFF position, which is the same as the alarm assertion position.
*7ME39400AL03 Mercury Relay only available with Normally Open.
Table A-4
Input/Output Wiring (TB4) - 7ME39400AL03 Expanded I/O Module
Pin#
Signal
1
2
3
4
5
AUX Io3+
6
AUX Io3-
7
AUX Io4+
8
AUX Io4-
Note
Auxiliary 4-20 mA loops are assigned and spanned under menu control of Vo and PGEN
outputs.
Figure A-4
Vc: 24 VDC Typical (+15 VDC to +30 VDC max) Loop Power
R
: 1000 ohms (max), Loop wire resistance plus user's input load resistance
L
I = 4-20 mA
40
Definition
No Connection
No Connection
No Connection
No Connection
Isolated Loop Power Io3
Io3 4-20 mA Output
Isolated Loop Power Io4
Io4 4-20 mA Output
7ME39400AL03 TB4 Expanded I/O Wiring
Description
Connect +30 V max. Loop Supply here
Vo1+ Data Presented as 4-20 mA
Connect +30 V max. Loop Supply here
Vo2+ Data Presented as 4-20 mA
FUT1010 IP65 NEMA 4X & IP66 NEMA 7 Liquid Quick Start