04.2006
Number / Alarm
Cause
A022
The threshold for initiating an alarm has been
exceeded.
Inverter temperature
A023
The parameterizable threshold for initiating an
alarm has been exceeded.
Motor temperature
A024
The motor has moved during motor data
identification.
Motor movement
A025
If the instantaneous load condition is
maintained, then the inverter will be thermally
I2t Inverter
overloaded.
A026
Ud is above the continuously permissible DC
link voltage for more than 30sec in a time
Ud too high
interval of 90sec
A029
The parameterized limit value for the I2t
monitoring of the motor has been exceeded.
I2t motor
A033
Bit 3 in r553 status word 2 of the septoint
channel. The speed actual value has
Overspeed
exceeded the value of maximum speed plus
the set hysteresis.
A034
Bit 8 in r552 status word 1 of the setpoint
channel. The difference between freqeuncy
Setpoint/actual value
setpoint/actual value is greater than the
deviation
parameterized value and the control
monitoring time has elapsed.
A035
The clockwise and/or the counter-clockwise
rotating field is not enabled, or a wire
Wire break
breakage is present in the terminal wiring
(both control word bits are zero).
Siemens AG
6SE7087-6KD60
SIMOVERT MASTERDRIVES
Operating Instructions
Counter-measure
- Measure intake air or ambient temperature.
- Observe the derating curves at theta >45°C
(Compact PLUS) or 40°C.
Check
- Whether the fan -E1 is connected and is
rotating in the correct direction.
-The air intake and discharge openings for
blockage.
- The temperature sensor at -X30.
- r833 indicates the maximum converter
temperature of all existing measuring points
(Compact/chassis type unit).
- r833.01 indicates the actual converter
temperature (Compact PLUS type).
Check the motor (load, ventilation, etc.). The
current temperature can be read in r009 Motor
Tmp.
Check the KTY84 input at connector
-X103:29,30, or -X104:29,30 (Compact PLUS
type) for short-circuit.
Lock the motor.
Check:
- P72 Rtd Drive Amps
- MLFB P70
- P128 Imax
- r010 Drive Utilizat
Motor load cycle is exceeded!
Check the parameters:
P382 Motor Cooling
P383 Mot Tmp T1
P384 Mot Load Limits
P804 Overspeed Hys plus
P452 n/f(max, FWD Spd) or
P453 n/f(max, REV Spd) has been exceeded
Increase the parameter for the maximum
frequencies or reduce the regenerative load.
Check
- whether an excessive torque requirement is
present
- whether the motor has been dimensioned too
small.
Increase values P792 Perm Deviation Frq/
set/actual DevSpeed and P794 Deviation Time
Check whether cable(s) to the corresponding
digital input(s) P572 Src FWD Spd / P571 Src
REV Spd is (are) interrupted or released
Faults and Alarms
14-19