04.2006
NOTICE
9.2.4
Parameterization by running script files
Description
NOTE
Siemens AG
6SE7087-6KD60
SIMOVERT MASTERDRIVES
Successful parameterization of the units by download is only ensured if
the unit is in the "Download" status when the data is being transferred.
Transition into this status is achieved by selecting the "Download"
menu in P060.
P060 is automatically set to 6 after the download function has been
activated in the OP1S or in the DriveMonitor service program.
If the CU of a converter is replaced, the power section definition has to
be carried out before parameter files are downloaded.
If only parts of the entire parameter list are transferred by download, the
parameters of the following table must always be transferred too, as
these automatically result during the drive setting from the input of other
parameters. During download, however, this automatic adjustment is
not carried out.
Parameter number
P109
P352
P353
Table 9-7
Parameters which always have to be loaded during download
If parameter P115 = 1 is set during download, the automatic
parameterization is then carried out (according to the setting of
parameter P114). In automatic parameterization, the controller settings
are calculated from the motor rating plate data and the reference values
P350 to P354 are set to the motor rated values of the first motor data
set.
If the following parameters are changed during download, they are not
then re-calculated by the automatic parameterization:
P116, P128, P215, P216, P217, P223, P235, P236, P237, P240, P258,
P259, P278, P279, P287, P291, P295, P303, P313, P337, P339, P344,
P350, P351, P352, P353, P354, P388, P396, P471, P525, P536, P602,
P603.
Script files are used to parameterize devices of the MASTERDRIVES
series as an alternative to downloading a parameter set. A script file is
a pure text file that must have the filename extension *.ssc . The script
file executes individual commands using a simple command syntax for
the purpose of device parameterization. (You can write the script files
using a simple text editor, such as WordPad.)
Please refer to the online help for the scriptfiles.
Operating Instructions
Parameter name
Pole pair number
Reference frequency = P353 x P109 / 60
Reference frequency = P352 x 60 / P109
Parameterizing Steps
9-41