Control Word and Status Word
Bit 16: Function data set FDS bit 0 command
Result
Bit 17: Function data set FDS bit 1 command
Result
Bit 18: Motor data set, MDS bit 0 command
Condition
Result
Bit 19: Motor data set, MDS bit 1 command
Condition
Result
Bit 20: Fixed setpoint FSW bit 0 (LSB) command
Result
Bit 21: Fixed setpoint FSW bit 1 (MSB) command
Result
Bit 22: Synchronizing enable command (H "synchronizing enable")
Condition
Result
10-6
♦ In conjunction with bit 17 "FDS BIT 1" one of the four possible
function data sets is energized.
♦ In conjunction with bit 16 "FDS BIT 0" one of the four possible
function data sets is energized.
READY TO POWER-UP (009), PRE-CHARGING (010) or READY
(011)
♦ One of the four possible motor data sets is energized in conjunction
with bit 19 "MDS BIT 1".
READY TO POWER-UP (009), PRE-CHARGING (010) or READY
(011)
♦ One of the four possible motor data sets is energized in conjunction
with bit 18 "MDS BIT 0".
♦ In conjunction with bit 21 "FSW BIT 1", one of the four possible fixed
setpoints is energized to input as percentage fixed setpoints,
referred to the reference frequency P352 or reference speed P353.
♦ In conjunction with bit 20 "FSW BIT 0" one of the four possible fixed
setpoints is energized for input as percentage fixed setpoints,
referred to the reference frequency P352 or the reference speed
P353.
♦ For converter sychronization (P534 = 1):
HIGH signal, TSY (option) available and P100 = 2 (V/f characteristic
for textile applications).
♦ For line synchronization (P534 = 2):
HIGH signal, TSY (option) P100 = 1, 2 or 3
♦ The command enables the synchronizing function.
6SE7087-6KD60
Operating Instructions
SIMOVERT MASTERDRIVES
04.2006