Carry out a functional test
1. Start drive
1. Start inverter: X3/DI1 = HIGH.
a) If the inverter is equipped with an integrated safety system: X1/SIA = HIGH and X1/SIB = HIGH.
2. Activate frequency preset 1 (20 Hz) as speed setpoint: X3/DI4 = HIGH.
The drive rotates with 20 Hz.
3. Optional: Activate reversal.
a) X3/DI3 = HIGH.
The drive rotates with 20 Hz in the opposite direction.
b) Now deactivate reversal: X3/DI3 = LOW.
Speed characteristic (example)
DI1
Drive follows frequency setpoint
AI1 [V]
10
0
DI4
Preset frequency setpoint 1 active
DI3
f [Hz]
set
60
50
20
0
5 s
-20
2. Stop drive
1. Now deactivate frequency preset 1: X3/DI4 = LOW.
2. Now stop inverter: X3/DI1 = LOW.
The functional test is completed.
Speed setpoint selection via X3/AI1 active
(In this example X3/AI1 is connected to GND)
5 s
Initial switch-on and functional test
Invert rotation active
Preset frequency
setpoint 1 (20 Hz)
Commissioning
t
t
t
t
t
187