Herunterladen Inhalt Inhalt Diese Seite drucken

3-Phase Mains Connection 400 V; Rated Data - Lenze i550 Montage- Und Einschaltanleitung

0.25 kw ... 132 kw 0.5 hp ... 175 hp
Vorschau ausblenden Andere Handbücher für i550:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

3-phase mains connection 400 V

Rated data

The output currents apply to these operating conditions:
• At a switching frequency of 2 kHz or 4 kHz: Max. ambient temperature 45°C.
• At a switching frequency of 8 kHz or 16 kHz: Max. ambient temperature 40 °C.
Inverter
Rated power
Rated power
Mains voltage range
Output voltage
Rated mains current
Without mains choke
With mains choke
Apparent output power
Rated output current
2 kHz
4 kHz
8 kHz
16 kHz
Power loss
2 kHz
4 kHz
8 kHz
16 kHz
For controller inhibit
Cyclic mains switching
Max. motor cable length
shielded
Without EMC category
Category C1 (2 kHz, 4 kHz, 8
kHz)
Category C2 (2 kHz, 4 kHz, 8
kHz)
Category C3 (2 kHz, 4 kHz, 8
kHz)
Weight
Weight
I55AE137F
I55AE155F
kW
0.37
hp
0.5
A
1.8
A
1.4
kVA
0.9
A
-
A
1.3
A
1.3
A
0.9
W
-
W
20
W
24
W
24
W
6
m
15
m
3
m
15
m
15
kg
0.8
lb
1.8
I55AE175F
I55AE211F
0.55
0.75
0.75
1
3/PE AC 340 V ... 528 V, 45 Hz ... 65 Hz
3 AC 0-400/480 V
2.5
3.3
2
2.6
1.2
1.6
1.8
2.4
1.8
2.4
1.8
2.4
1.2
1.6
24
30
25
32
31
40
31
40
6
6
3 times per minute
50
50
3
3
20
20
20
20
1
1
2.2
2.2
Technical data
3-phase mains connection 400 V
I55AE215F
I55AE222F
1.1
1.5
1.5
2
4.4
5.4
3
3.7
2.2
2.6
3.2
3.9
3.2
3.9
3.2
3.9
2.1
2.6
38
45
40
48
51
61
51
61
6
6
50
50
-
-
20
20
35
35
1.35
1.35
3
3
Rated data
2.2
3
7.8
5.3
3.8
5.6
5.6
5.6
3.7
62
66
85
85
6
50
-
20
35
1.35
3
197

Quicklinks ausblenden:

Werbung

Kapitel

Inhaltsverzeichnis
loading

Inhaltsverzeichnis