Functional description

d The module monitores the complete panel power supply and controls temperature and time
depending the battery charging.
d The key enables the manual startup of the battery charging, e.g. if the battery voltage is less than
22 V and enables with charged batteries the panel startup without main power.
Wiring
Pos. Marking
1
AUX1 +
2
AUX1 -
3
AUX2 +
4
AUX2 -
5
AUX3 +
6
AUX3 -
7
AUX4 +
8
AUX4 -
9
AUX5 +
10
AUX5 -
11
AUX6 +
12
AUX6 -
13
MAIN +
14
MAIN -
15
FAULT
17
BAT1 +
18
BAT1 -
19
BAT2 +
20
BAT2 -
21
BAT FAULT -
22
BAT FAULT +
23
AC FAULT -
24
AC FAULT +

Technical Specification

Indication / operating elements
Voltage supply
Current consumption at 24V DC
Current supply of module rails
PRS 0002 / PRD 0004
Safety standards
Outputs
EMI / EMC protection
Permissible operating temperature -5 _C . . . 50 _C
Permissible storage temperature
Permissible relative humidity
Housing material and color
Dimensions (H x W x D)
Weight
Product description BCM 000 A
Connection
Switched output +24 V / max. 1.4 A
Switched output +24 V / max. 1.4 A
(battery supported)
Switched output +24 V / max. 1.4 A
Switched output +24 V / max. 1.4 A
(battery supported)
Switched output +24 V / max. 1.4 A
Switched output +24 V / max. 1.4 A
(battery supported)
Consumer, +24 V / max. 0.5 A
Consumer, +24 V / max. 0.5 A
(battery supported)
Consumer, +24 V / max. 0.5 A
Consumer, +24 V / max. 0.5 A
(battery supported)
Consumer, +24 V / max. 0.5 A
Consumer, +24 V / max. 0.5 A
(battery supported)
Power Supply Unit
Power Supply Unit
Main Power Fault Signal
Batteries 1 + 2 plus
Batteries 1 + 2 minus
Batteries 3 + 4 plus
Batteries 3 + 4 minus
Battery Power Fault Signal
Battery Power Fault Signal
Power Supply Unit Fault Signal Output
Power Supply Unit Fault Signal Output
1 LED green (Mains On)
3 LEDs yellow (Mains fault , Batteries 1 fault / Batteries 2 fault)
1 Key (Batteries charging, Panel startup without mains power)
20 V DC - 30 V DC (min - max)
31 mA (Stand-by mode) / 40 mA (in case of malfunction)
Max. 6 A from Mains
Max. 8 A Battery power
IEC 60950 / EN 60950
3 Switches (+24 V/1.4 A), battery supported
3 Consumer (+24 V/0.5 A), battery supported
1 Battery Power Fault Signal (0 V / 500 mA)
1 Power Supply Unit Fault Signal Output (0 V / 500 mA)
EN 50130-4 / EN 61000-6-3 / UL 864 / FCC Part 15
-20 _C . . . 60 _C
max. 95 % non condensing
ABS plastics, semi gloss anthrazit, RAL 7016
approx. 127 x 96 x 60 mm (approx. 5.0 x 3.8 x 2.4 inches)
approx. 185 g (approx. 6.5 ounces)
1 2 3 4 5 6 7 8 9 10 11 12
13 14 15
(23 _F . . . 122 _F)
(-4 _F . . . 140 _F)
15 / 32
4.998.137.261
17 18 19 20 21 22 23 24
4.998.153.971 / A5 / 06.2008