Staircase control unit THZ
These instructions must be followed in order to ensure the safety of persons.
Eliminate all the faults in the system immediately.
X
Always keep the mounting instructions at hand near the control unit.
X
Duties of the owner-operator
Protect the workplace against unauthorised entry.
X
Ensure that mounting, commissioning and maintenance are only carried out by qualified personnel author-
X
ised by GEZE. GEZE shall not be liable for injuries or damage resulting from unauthorised modification of the
equipment.
Ensure that the keys for the RWA switch are only available for instructed personnel.
X
Electrical system
Before working on the electrical system, disconnect the power supply (mains and battery), check that it is not
X
live and secure it against being switched on again.
Ensure that the connection to the power supply is only carried out by a qualified electrician. The power con-
X
nection and safety earth conductor test must be carried out in accordance DIN VDE 0100-600 or in accordance
with National Standards for countries other than Germany.
Use an on-site, 2-pole automatic circuit breaker with locking option, according to the permissible current car-
X
rying capacity of the cable, as the disconnecting device on the mains side.
After the system housing has been opened, live parts are exposed. The connecting terminals for system compo-
nents in parts have a low voltage of ≤50 V.
Do not the activate the mains and battery voltage until all the system components have been connected.
X
When replacing the batteries use only batteries approved by GEZE.
X
Ensure that the control unit cannot be opened by unauthorised persons.
X
Use only cables prescribed in the cable plan. Lay screening in accordance with the wiring diagram.
X
Specify cable types (e.g. fire protection cables) and required degree of protection in agreement with the local
X
inspection authority.
Always use insulated wire-end ferrules for wire cores.
X
Insulate unused wires.
X
Secure loose cables with cable ties.
X
Maintenance
A safety-related test with maintenance has to be carried out by GEZE-authorised specialist as required – at least
once every 12 months. You are given written proof of the test. All the batteries have to be replaced at the latest
after 4 years.
Spare parts
GEZE shall not be liable if products from other manufacturers are used with GEZE equipment.
Use only original GEZE parts for repair and maintenance work.
X
Regulations and standards
Warranty claims require mounting, installation and maintenance in accordance with the manufacturer's speci-
fications by a specialist company. Observance of all the relevant statutory regulations and instruction in correct
operation lie in the responsibility of the owner-operator or the installer commissioned by the owner-operator
respectively.
Maintain the system in accordance with the statutory regulations.
X
Observe the maintenance specifications.
X
Observe the latest versions of guidelines, standards and country-specific regulations, in particular:
X
à ASR A1.7 "Guidelines for doors and gates"
à DIN VDE 0100-600 "Setting up of low-voltage installations"
à DIN EN 60335-2-103 "Safety of electrical devices for home use and similar purposes; special requirements
for drives for gates, doors and windows"
à Accident prevention regulations, in particular DGUV Regulation 1 "Accident prevention regulations,
principles of prevention" and DGUV Regulation 3 "Accident prevention regulations, electrical systems and
equipment".
à VDE 0833 "Alarm systems for fire, intrusion and hold-up"
à VDE 0815 "Wiring cables for telecommunication and data processing systems"
à MLAR "Model Guideline for Line Systems"
The measures for security and prevention of crushing, impact, shearing or drawing-in spots, in particular at
X
points with a height of less than 2.5 m are to be considered and carried out.
One measure is, for example, to use a switch with an OFF default setting (for example GEZE vent switch LTA-
LSA Mat. No. 118476). In the case of children or persons with a limited ability to judge, a key-operated switch
with an OFF default setting has to be used (e.g. GEZE Mat. No. 117996 for SCT, 090176 for cylinder). The switch
has to be mounted so that the points of danger can be seen.
Safety instructions
29