Control connections
3
Terminal Use
Voltage
X1/⊥24
supply
X1/+24
X1/+O24 Supply voltage for digital
Digital
X3/I1
inputs
inputs
X3/I8
Digital
X2/O1
outputs
outputs
X2/O4
40
0 V of supply voltage,
ground for digital inputs
and outputs
Supply voltage
outputs
Freely assignable input 1
Freely assignable input 8
Freely assignable output 1
Freely assignable output 4
EDK10200EV3 DE/EN/FR 6.0
Level
Data
-
-
+18 VDC ... 30 VDC
-
+18 VDC ... 30 VDC
-
Input current: 8 mA at 24 V
Reading and processing the
Reading and processing the
HIGH active
HIGH active
inputs: shortest reading cycle:
LOW: 0 V ... +4 V
1 ms (depending on the site
1 ms (depending on the site
HIGH: +13 V
HIGH: +13 V ... +30 V
+30 V
where the process map is
generated)
Load capacity: max. 1 A per
output
output
HIGH active
HIGH active
Updating the outputs: shortest
LOW: 0 V ... +4 V
update cycle is 1 ms (depending
update cycle is 1 ms (depending
HIGH: +13 V
HIGH: +13 V ... +30 V
+30 V
on the site where the process
map is generated)