2.2.4.2
Input contacts (photocoupled)
The connections of the inputs listed below refer to the 18-pole terminal board J5, with numbering starting from
pin 1 from the left. The base of the terminal board also bears the text of the corresponding inputs.
-
I 1: Pins 16 and 17
-
I 2: Pins 15 and 16
-
I 3: Pins 13 and 14
-
I 4: Pins 12 and 13
The inputs can be activated in DC or AC (50-60 Hz). The following table shows the electrical specifications of
the inputs: Table 7.
Minimum activation voltage [V]
Maximum deactivation voltage [V]
Maximum admissible voltage [V]
Current absorption at 12V [mA]
Max. admissible cable section [mm²]
N.B. Inputs can be controlled with both polarities (positive or negative with respective return to earth)
ENGLISH
Figure 12: Example of output connections
Input specifications
Table 9: Input specifications
87
With reference to the example in Figure 10 and
using the default settings (O1 = 2: contact NO;
O2 = 2; contact NO) the following is obtained:
L1 lights up when the pump is blocked
(e.g. "BL": water failure block).
L2 lights up when the pump is running
("GO").
DC inputs [V]
8
2
36
3,3
2,13
AC inputs 50-60 Hz
[Vrms]
6
1,5
36
3,3