Herunterladen Inhalt Inhalt Diese Seite drucken

ABB TTF300 Inbetriebnahmeanleitung Seite 60

Für feldmontage
Vorschau ausblenden Andere Handbücher für TTF300:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 1
Electrical connections
4.4.1.4
Non-insulated sensor measuring inset (thermocouple), transmitter housing grounded
The shield of the sensor connecting cable is grounded via the grounded sensor housing. This
shield is insulated from the transmitter housing.
The shield of the power supply cable is grounded at the supply isolator / PCS input directly. This
shield is insulated from the transmitter housing.
The shields of the power supply cable and the sensor connecting cable must not be connected
to one another.
Make sure that the shields are not connected to ground anywhere else.
1
8
Fig. 12: Shields of the sensor connecting cable and the power supply cable are separate and each grounded at
one end
1 Temperature sensor
2 Shield grounded via sensor
3 Sensor connection cable
4 Shield insulated from transmitter housing
5 Transmitter housing, grounded
22 - EN
8
2
3
4
5
6
6 Shield insulated from transmitter housing
7 Power supply cable
8 Grounding point
9 Supply isolator / PCS input
TTF300
9
7
8
CI/TTF300-X1
A00274

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis