Herunterladen Inhalt Inhalt Diese Seite drucken

bürkert SE 56 Bedienungsanleitung Seite 31

Vorschau ausblenden Andere Handbücher für SE 56:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

where fs
is the maximum full scale value corresponding to the sensor, equal to a 10m/s liquid
max
speed. The measure units are shown as appear on the display. The British and American units are
diversified by using capital and small characters.
3
cm
Cubic centimetre
ml
Millilitre
l
Liter
3
dm
Cubic decimeter
dal
Decalitre
hl
Hectolitre
3
m
Cubic metre
When a measure mass unit is set, the specific gravity function is automatically enabled by the system.
Please, note that the mass measure is heavily affected by the temperature. With certain liquids this
may cause significant measurement errors. The following measure of time units can be selected: s =
second, m = minute, h = hour, d = day.
(POS. 2.3) Measure unit and decimal totalizers number
Setting the measure unit and decimals number for visualized totalizers or the volumes to batch.
Setting the measure unit and decimals places number displayed for the volumes. To set the measure
unit, position the cursor on field of the measure unit. To set the unit type, position the cursor on the
blank space between the measure unit and the numeric value; the number decimal places can be
selected by placing the cursor on numeric field and choosing one of the possible combinations: 1000-
01.00-001.0-00001.
(POS. 2.4-5) Pulse value channel 1-2 and unit of measure of tot.
This function allows the user to set a signal (a pulse) to be given from the transmitter when a defined
amount of liquid has passed through the sensor. To set the parameter, complete the three fields,
from left to right: 1) measure unit, 2) unit type and 3) numeric value. The selection is performed by
positioning the cursor in the field to be modified. To change the unit type (metric, British or American,
mass or volume) position the cursor on the blank space between the measure unit and the numeric
value. When the nominal diameter is set to zero it is possible to modify only the numeric field since
the measure unit stays at meters (m) or feet (ft). Only those units described above are available to be
selected.
(POS. 2.6-7) Pulse duration channel 1-2
With the liquid volume to generate the pulse value (pos 2.4-5) set by the user. The user must set the
corresponding duration of the pulse to be outputed. This value is expressed in milliseconds and has to
be between 0.4 and 9999.99. When the high frequency output is present, then the minimum value
can type of device is connected to the transmitter, the user must verify that the set pulse duration is
compatible with the external device processing such pulses. If, for example, an electro-mechanical
pulse counter is connected, one of be set to a minimum of 0.04 milliseconds. ATTENTION: since the
transmitter can not detect which two problems may occur; firstly, if the pulse is too long the coils may
burn out, secondly, if the pulse is too short, the counter may not be able to function, with the
possibility of causing damage of the output.
3
in
Cubic inch
Gal
American gallon
GAL
British gallon
3
ft
Cubic foot
Bbl
Standard barrel
BBL
Oil barrel
3
yd
Cubic yard
kgl
KAmerican gallon
KGL
KBritish gallon
31
G
Gram
Kg
Kilogram
T
Ton
Oz
Ounce
Lb
Pound
Ton
short tons
[Tot.MU:dm³X.XXX]
dm³
[Pls1-2=
X.XXXXX]
[Tpls1-2=msXXXX.XX]
SE 56

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis