Installing sensors in Reflect mount
Reflect mount - Sensor installation using mounting frames and spacer bar
1. Use the Wizard setup procedure to program the meter for application parameters such as pipe size, liquid type, and
sensor size. Once entered the transmitter will return a spacing index number appropriate for the application.
2. Using the supplied space bar, set the distance between the sensors according to the spacing index number provided by
transmitter. The spacing index provides the correct distance apart for the sensors based on the pipe size given.
Before continuing refer to the Reflect mount installation diagram example below.
Sensor clamping screw
Customer pipe
7ME39600*** Mounting Frame
Spring Clip (not present on some mounting frame models)
Spacer bar
Figure 3-2
Reflect mount
3.3

Terminal Layout

Figure 3-3
Terminal layout - wall mount housing
8
Spacer bar pin and reference hole
Mounting strap
Larger pipes may need additional mounting straps
Orientation for Single path sensor at the 9 o'clock
position
Orientation for Dual path sensor at the 10 and 2
o'clock positions
SITRANS FS230