6.3.3.19 Preset value
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
preset value function PNU 65000, see 132.
The zero point of the measuring system can be adapted to the mechanical zero point via the Preset
value parameter and is set either as an absolute value or as a relative value, in relation to the
position output, during execution of the preset function, see chapter "Preset function" on page 145.
Data type
Integer32, two's complement
31
-2
Lower limit
31
Upper limit
+2
Default
0