2. Safety Instructions
The device shall only be
used for its intended pur-
pose and in undamaged and
perfect condition!
Only genuine CEAG spare
parts may be used for re-
placement and repair!
When working on the emer-
gency luminaire first cut off
mains (charging phase and
L') and interrupt battery
operation. Fig. 11 shows the
indication label on the
emergency luminaire.
Prior to its initial operation,
the luminaire will have to be
checked in accordance with
the instructions as per
section Installation!
Carry out the marking of the
emergency luminaire: As-
sign the circuit, the luminaire
No. and ID-No. and enter
them.
The manual log book shall be
performed in compliance with
the national regulations. It is
not applicable by automatical
log book with the CG-Con-
troller CGLine!
Any foreign matter shall be
removed from the luminaire
prior to its initial operation!
Observe the national safety
rules and regulations for pre-
vention of accidents as well
as the safety instructions
included in these operating
instruction marked with
3. Conformity with
Standards
Conforms to: EN 60 598-1,
EN 60 598-2-22, EN 1838, DIN
VDE 0108/10.89.
Low-voltage directive 93/68/
EEC, EMC directive 89/336/
EEC.
Note: In spite of CE conformity,
there may be a mutual
influence on equipment and
luminaires.
Developed, manufactured and
tested in accordance with DIN
EN ISO 9001.
4. Technical data
Input voltage:
230/240 V AC
Rated current
(AC):
70 mA
Power con-
sumption (AC): max. 16 VA
Lamp:
8 W/T16
Rated lumi-
nous flux of
the lamp:
450 lm
Rated lumi-
nous flux:
40% (phi
at the end of operating cycle
Insulation
class:
I I
Protection
category acc.
to EN 60529:
IP 41
At option:
IP 54
Accu:
gas-tight,reloadable,
maintenance-free
Rated operating cycle:
1h: NC-accu 3,6V, 1,5Ah
3h: NC-accu 3,6V, 4,0Ah
Admissible ambient
temperature
maintained light:
- 5°C...+35°C
non maintained light:0°C...+30°C
Supply
terminals:
3 x 2,5 mm²
Bus terminals:
2 x 1,5 mm
Weight: 28011-1/D
28011-3/D
28021-1/D
28021-3/D
Dimensions:
see dimensional
drawing on page 4
9
Fig. 11
4.2 Brief Description/Area
of Application
As a self-contained luminaire the
STYLE Variant 28011/28011
emergency and safety lumi-
naire is suitable for installations
according to VDE 0108.
With the CEAG CG-Controller
CGLine 400 the self-contained
luminaires can be monitored
centrally via a bus cable.
5. Installation
For the mounting and
operation of electrical
apparatus, the respec-
50 Hz
tive national safety regulations
as well as the general rules of
engineering will have to be
observed.
5.1 Assembly
Style Variant 28011
Loose the snap hooks of the
legend cover with a qualified
/phi
)
E
nominate
slot-headed screwdriver
(Picture 3) and lift the cover
from the enclosure. Remove
the lamp from the socket.
Loose the 4 screws with a
cross-slotted screwdriver and
lift the top part of enclosure
from the lower part. According
to assembly conditions tweak
out optional the impressed
cable entries sideways or on
the backside. Enter the
sealing stopper and stamp or
cut out a hole for the using
cable diameter. If the sealing
lips are damaged, replace the
2
cable entries to maintain the
1,7kg
1,9kg
protection. Unused cable
1,6kg
entries which are tweaked out
1,8kg
must be closed with sealing
stoppers (IP - degree of
protection). Insert the cable in
the body of the lamp and