1. Safety Instructions

r The device shall only be
used for its intended pur-
pose and in undamaged
and perfect condition!
r Only genuine CEAG spare
parts may be used for re-
placement and repair!
r When working on the emer-
gency luminaire first the sys-
tem must be blocked, battery
operation must be interrupted
and mains must be cut off.
Fig. 4 shows the indication
label on the emergency lumi-
naire.
r Carry out the marking of the
emergency luminaire: As-
sign the circuit and the lumi-
naire No. and enter them.
r Log book records shall be
kept in compliance with the
national regulations.
r Any foreign matter shall be
removed from the luminaire
prior to its initial operation!
r While undertaking any serv-
icing on the luminaire, the
national safety rules and regu-
lations for prevention of ac-
cidents shall be observed as
well as the safety instructions
included in these operating
instructions marked with a
2. Conformity with
standards
Luminiare for emergency ligh-
ting acc. to EN 60 598-2-22 for
connection to safety luminaire
systems acc. to DIN VDE 0100-
718, EN 50 172 and E DIN VDE
0108-100. Used ECG is con-
form to:
EN 60 929, EN 61 347-2-3 and
EN 61 347-2-4.
Designed, manufactured and
tested according to DIN EN ISO
9001.
3. Product
description
3.1 Brief description/
Scope of application
Exit or safety luminaire, suitable
for operation on CEAG safety
lighting systems with single
luminaire monitoring (Cewa-
Guard-Technology) and/or with
programmable switching mode
in the outgoing circuit (STAR-
technology).
The SL/RZ 3301 is not fitted with
monitoring electronic and so neit-
her addressable nor switchable.

3.2 Technical data

Dimensions without lamp
(ØD)/H:
132 mm/60 mm
Ceiling cut-out: Ø 112 ± 1 mm
Exit cube
(L x H x W)/mm: 242 x 227 x 242
Material of
enclosure:
Plastics
Type of mounting: wall or ceiling
mounted
Weight (incl.
cube):
2.26 kg
Terminals:
3 x 2 x 2.5 mm²
Power input:
220-240 V
50/60 Hz
176 - 275 V DC
Standby power loss:
< 0.5W
Rated current (DC)
TC DEL 10 W: 0.035 mA
TC DEL 13 W: 0.050 mA
Power consumption (AC)
TC DEL 10 W: 16 VA
TC DEL 13 W: 23 VA
Power factor:
0.6
Inrush current: 3A/ms
Operating
frequency:
44kHz
Perm. ambient
temperature:
- 10 °C ..+ 40°C
Lamp:
10 W/TC DEL
13 W/TC DEL
Rated luminous flux for
emergency
operation:
75 % (phi
Insulation
class:
II
Protection category acc.
to EN 60527:
IP 20
)
mains