Mechanical installation
Standard devices in the power range 0.37 ... 11 kW

Mounting in "cold plate" technique

4.1.4
Mounting in "cold plate" technique
The drive controllers can be mounted in ˜cold plate˜ technique, e.g. on collective coolers.
For this purpose, the drive controllers of type EVS93xx−Cxx must be used.
Mounting material required from the scope of supply:
Description
Fixing bracket
Sheet metal screw
3.5 × 13 mm (DIN 7981)
Requirements for collective coolers
The following points are important for the safe operation of drive controllers:
Good thermal connection to the cooler
ƒ
– The contact surface between collective cooler and drive controller must be at least
as large as the cooling plate of the drive controller.
– Flat contact surface, max. deviation 0.05 mm.
– Connect the collective cooler with all specified screw connections with the drive
controller.
Do not exceed the thermal resistance R
ƒ
operation of drive controllers under rated conditions.
9300
Type
EVS9321−Cx
EVS9322−Cx
EVS9323−Cx
EVS9324−Cx
EVS9325−Cx
EVS9326−Cx

Ambient conditions

The rated data and the derating factors at increased temperature also apply to the
ƒ
ambient temperature of the drive controllers.
Temperature at the cooling plate of the drive controller: max. 75 °C.
ƒ
132
Use
Controller fixing
Mounting the fixing bracket
to the controller
given in the table. The values apply to the
th
Cooling path
Power to be dissipated
P
[W]
v
24
42
61
105
180
360
l
Quantity
EVS9321−Cx
EVS9323−Cx
EVS9322−Cx
EVS9324−Cx
2
2
6
6
Heatsink − environment
R
[K/W]
th
1.45
0.85
0.57
0.33
0.19
0.10
EDKVS9332X DE/EN/FR 4.0