6. Display and operating unit, model DI-PT-U
6.5 Setting the additional display
The additional display can indicate the following values:
Pressure
■
EN
Level
■
Volume
■
Current
■
PV percent
■
Sensor temperature Temperature at the sensor is displayed.
■
PV (primary value) The value corresponding to the mode will be displayed.
■
Drag pointer values
P
/ P
■
min
max
PV
/ PV
■
min
T
/ T
■
min
max
Further data
TAG short (max. 8 capital letters and figures)
■
TAG long (max. 32 alphanumeric characters)
■
Empty (additional display switched off)
■
1. Open the operating menu with [↵].
Select "Display" and confirm with [↵].
2. Select "Add. display" and confirm with [↵].
3. Select value and confirm with [↵].
» Additional display indicates the selected value.
24
Applied pressure is displayed.
Level is displayed.
Volume is displayed.
Output signal is displayed.
Output signal is displayed as a percentage.
If the mode is changed, then the main display will change.
max
WIKA operating instructions process transmitter, model UPT-2x