4.4
Settings parameters, examples
Examples for setting the Eco Message parameters via Additional information/message string
The examples listed below are based on the following standard parameter setting:
– Pt100, 4-wire, lower range value 0 °C, upper range value 100 °C, error current 22 mA, damping 0 s, mains filter 50 Hz, error delay 5 s,
line break and short-circuit monitoring active, parameter read-out level 1 active or
&1PT100 WN4 FC22 MF50
(start of range, end of range, unit, damping, additional information/message (&+codes) are the universal/generic parameters of temperature
transmitters)
Example 1
Parameter setting: Pt 100, 3-wire, error current 3.6 mA, mains filter 60 Hz
Write:
Enter the following parameters in the additional information/message field and write to device:
Read:
Make operator device / software read.
Example 2
Parameter setting: Thermocouple Type K, internal RJ active (standard,
need not be written)
Write:
Enter the following parameters in the additional information/message field and write to device:
Read:
Make operator device / software read.
Example 3
Parameter setting: Pt 100, 2-wire, 1.1 ohms sensor line resistance,
error current 23.2 mA, error delay 3 s
Write:
Enter the following parameters in the additional information/message field and write to device:
Read:
Make operator device / software read.
You have to change over to the second read level to be able to read its
parameter values:
Write:
Enter the following parameters in the additional information/message field and write to device:
Read:
Make operator device / software read.
Example 4
Parameter setting: Resistance measurement 0...5 kohms, 4-wire, error current 23 mA,
error delay 7 s
(for resistance linear and voltage linear please observe the specifications and information
in the table)
Write:
Enter the following parameters in the additional information/message field and write to device:
Read:
Make operator device / software read.
You have to change over to the second read level to be able to read its parameter values:
Write:
Enter the following parameters in the additional information/message field and write to device:
Read:
Make operator device / software read.
3KDE115000R4284
Temperature Transmitter TH01, TH01-Ex, TH101, TH101-Ex
&PT100 WN3 FC3.6 MF60
----> Result:
&1PT100 WN3 FC3.6 MF60
&TK
----> Result:
&1TK CI FC22 MF50
&PT100 WN2 WR1.1 FC23.2 FD3
----> Result:
&1PT100 WN2 WR1.1 FC23.2
&2
----> Result:
&2FD3 /DTW /WMBS
&RH WN4 FC23 FD7
&1RH WN4 FC23
----> Result:
&2
----> Result:
&2FD7 /DT /WMB
Programming
33