Electrical installation
Standard devices in the power range 75 ... 90 kW
Mains connection
5.5
Standard devices in the power range 75 ... 90 kW
5.5.1
Mains connection
(
Stop!
ƒ
ƒ
ƒ
0
1
4
T1
2,5 Nm
T2
22.1 lb-in
PE
PE
+UG
L1 L2 L3
M10
+UG, -UG
30 Nm
PE
264 lb-in
158
Only connect the controller to the permitted mains voltage (^ Technical
data). A higher mains voltage destroys the controller!
Some controllers may only be actuated with a mains choke or mains filter.
This requirement can differ with regard to operation at rated power and
operation at an increased rated power.
The leakage current to earth (PE) is > 3.5 mA. In accordance with
EN 61800−5−1 a fixed installation is required. The PE conductor has to be
designed double.
3/PE AC 400V
PE
PE
l
+UG
-UG
L1 L2 L3
M10
L1, L2, L3
30 Nm
+UG, -UG
264 lb-in
PE
3/PE AC 400V
E82EV753K4:
6-12 Nm (53.1-106.2 lb-in)
L1, L2,
E82EV903K4:
L3
10-20 Nm (88.5-177 lb-in)
L1 L2 L3
3
l
-UG
0
Connection for mains choke
1
Connection for footprint mains filter
2
Connection for built−on mains filter
3
Connection for braking unit^ Documentation of braking unit)
4
Temperature monitoring connection for mains filter (thermal contact
Z1
Mains choke/mains filter
l
3/PE AC 400V
L1
3
L2
L3
N
PE
Z1
2
+UG
PE
3/PE AC 400V
L1 L2 L3 PE
L1' L2' L3'
Netz / Line
Gerät / Load
Z1
PE
L1
L2 L3
T1
4
J>
T2
3
L1
L2
L3
-UG
3
PE
l
+UG
-UG
L1 L2 L3
M10
L1, L2, L3
30 Nm
+UG, -UG
264 lb-in
PE
8200vec290
EDK82EV903 DE/EN/FR 4.0