3
Technical data
3.1
General data and operating conditions
Conformity and approval
Conformity
CE
Approval
UL
Protection of persons and equipment
Type of protection
Earth leakage current
Insulation of control
circuits
Insulation resistance
Protective measures
EMC
Noise emission
Interference immunity
1)
Motor cable lengths depend on the inverter type and the switching frequency
EDK82EV903 DE/EN/FR 4.0
General data and operating conditions
2006/95/EC
Low−Voltage Directive
2004/108/EG
EMV Directive
cULus
Power Conversion Equipment (File No. E132659)
EN 60529
IP20
IP41 on the heatsink side for thermally separated mounting
(push−through technique).
NEMA 250
Protection against contact in accordance with type 1
IEC/EN 61800−5−1
> 3.5 mA
IEC/EN 61800−5−1
Safe mains isolation through double (reinforced) insulation
IEC/EN 61800−5−1
< 2000 m site altitude: overvoltage category III
> 2000 m site altitude: overvoltage category II
Against short circuit, earth fault (protected against short to
earth on power−up, limited protection against short to earth
during operation), overvoltage, motor stalling, motor
overtemperature (input for PTC thermistor or thermal
contact, I
IEC/EN 61800−3
Cable−guided, category C1 or C2 when using shielded motor
1)
cables
interference suppression or additional RFI/mains filter
0.25 ... 11 kW
E82xVxxxKxC0xx
E82xVxxxKxC2xx
15 ... 90 kW
E82EVxxxK4B3xx
E82xVxxxK4B2xx
IEC/EN 61800−3
Category C3
l
Technical data
Observe stipulations and safety
instructions!
2
t monitoring)
, dependent on the device variant with integrated
no additional measures
with external filter techniques
no additional measures
with external filter techniques
3
121