5
Electrical installation
Standard devices in the power range 45 ... 55 kW
Fuses and cable cross−sections according to UL
5.4.3
Fuses and cable cross−sections according to UL
Supply conditions
Range
Fuses
Cables
Observe all national and regional regulations!
Operation at rated power
8200 vector
Type
Mains 3/PE AC 400/500 V − operation without mains choke/mains filter
E82xV453K4B
E82xV553K4B
Mains 3/PE AC 400/500 V − operation with mains choke/mains filter
E82xV453K4B
E82xV553K4B
Operation with increased rated power
Operation at an increased rated power is not UL−certified.
156
Description
l
Only according to UL 248
l
Mains short−circuit current up to 10000 A
l
Mains short−circuit current up to 50000 A
l
Only in accordance with UL
l
The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 75 °C
– Ambient temperature < 40 °C
Fuse
Type
[A]
Operation only permitted with mains choke or mains filter
100
125
l
: All classes permissible
rms
: Only classes "J", "T" or "R" permissible
rms
Rated fuse current / cable cross−section
L1, L2, L3, PE
Type
[AWG]
[A]
1
1/0
Circuit−breaker
L1, L2, L3, PE
[AWG]
EDK82EV903 DE/EN/FR 4.0