Commissioning

Make sure that the total nominal power of all connected con-
sumers does not exceed the capacity of the UPS system.
1. Connect the consumers to the UPS system without switching
them on.
2. Plug the power cable of the UPS system into an outlet (includ-
ed in the scope of supply of ZINTO E 3000). The display of the
UPS system lights up and shows "StbY."
3. Keep the button
onds.
4. If the display
restart the UPS system, if necessary. (See Troubleshooting.)
5. Make sure that "NORM" is displayed on the display. This indi-
cates that the UPS system is working in normal mode and the
consumers are being provided with power.
When starting for the first time, the output frequency is set to
the value of the input frequency (the automatic detection is
enabled by default).
6. If an additional emergency-off switch was installed, the emer-
gency-off function must also be checked:
7. Switch on the consumers one after the other.
The internal batteries will charge up to 90% of their capacity
in less than three hours. ONLINE recommends charging the
batteries for 48 hours after installation or after a longer peri-
od of storage.
ZE1000-3000_manual_ger_eng_it_V1.0.3
NOTE
on the UPS system pressed for three sec-
lights up, remedy all warning messages and
NOTE
NOTE
53 / 120
........................................................................
I N S T A L L A T I O N