Mounting and Connection Instructions AXS4Secure
10.
Connection diagram
10.1
Computer/connection PCB
Ethernet (10/100)
RJ45
AO1
4 semi-
AO2
conductor
AO3
outputs
AO4
0 V
AI1
0 V
AI2
0 V
4 analog
inputs
AI3
0 V
AI4
0 V
10.2
Connection of readers
The 4 RS-485 interfaces are designed for the connection of one reader per interface.
The following allocation is fixed:
o
Controller 1 --> Reader door 1 outside
o
Controller 2 --> Reader door 1 inside
o
Controller 3 --> Reader door 2 outside
o
Controller 4 --> Reader door 2 inside
For readers without DIP switch the address 1 is set automatically.
For readers with DIP switch the address 1 must be set manually.
Computer/connection PCB
AXS4Secure
Fuses:
Si1
1AF
O
perating voltage Controller 1
Si2
1AF
Operating voltage Controller 2
Si3
1AF
Operating voltage Controller 3
Si4
1AF
Operating voltage Controller 4
Si5
0.5 AF
E
xternal user 2
Si6
0.5 AF
External user 1
S1
Si3
+12 V DC
0 V
B (D-)
RS-485
A (D+)
Controller 3
Si4
+12 V DC
0 V
B (D-)
RS-485
A (D+)
Controller 4
--> address 1
--> address 1
--> address 1
--> address 1
Abort
Revision
TA1
TA2
Si1
+12 V DC
0 V
B (D-)
RS-485
A (D+)
Controller 1
Si2
+12 V DC
0 V
B (D-)
RS-485
A (D+)
Controller 2
Si5 Si6
33
Connection to
power supply unit
Fault
+12 V DC
0 V
Mains
USB master port
for
firmware update
Rel2
8 A/250 VAC
CC
5 A/30 VDC
NOC
NCC
Rel1
8 A/250 VAC
CC
5 A/30 VDC
NOC
NCC
Ext. user
+12 V DC
U_ext. 1
0 V
+12 V DC
U_ext. 2
0 V