26
3.
Function description
3.1
Analogue inputs
The AXS4Secure has 4 analogue inputs with a voltage 8 V DC, stabilized.
End-of-line resistor: 12k1, monitoring range: ±40%.
- Input 1:
Connection of door strike monitoring contact and door strike push button, door 1
- Input 2:
Connection of door strike monitoring contact and door strike push button, door 2
Evaluation inputs 1 and 2:
Value
12k1
Break
Short circuit
- Input 3:
Tamper input for panel cover contact and tear-off protection
- Input 4:
unused
The function of the inputs is fixed. All 4 inputs must be terminated with 12k1.
3.2
Semiconductor outputs
4 semiconductor outputs, aktive HIGH, 12 V DC / 50 mA
- Output 1: Door break-in door 1 or door 2
- Output 2: Holdup code door 1 or door 2
- Output 3: Tamper on reader door 1, door 2 or input 3
- Output 4: Mains- or battery fault
The function of the outputs is fixed.
3.3
Relay outputs
2 relay outputs for activation of door strikes.
Switching capacity max. 8 A / 250 V AC, 5 A / 30 V DC, min. 10 mA / 5 V DC
Mounting and Connection Instructions AXS4Secure
State
Idle state
(Door closed, DS push button not pressed)
Door open
DS push button pressed
Wiring
DS monitoring contact
Impulse 5 sec.
Impulse 5 sec.
Active as long as the event is present.
Active as long as the event is present.
(signal mains fault 20 sec. delayed)
DS push
12k1
button