Herunterladen Inhalt Inhalt Diese Seite drucken

Lenze E82ZAFAC010 Montageanleitung Seite 34

Application - i o pt
Vorschau ausblenden Andere Handbücher für E82ZAFAC010:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

4
Electrical installation
X3.1/
Signal type Function
1U/2U Analog
inputs
1I/2I
X3.2/
Signal type Function
Analog
62
outputs
63
9
1)
Output level 0 ... + 10 V or 0/+4 ... +20 mA: Adapt offset (C0422) and gain (C0420).
34
Actual or setpoint inputs (master voltage)
Use jumper and C0034 to change range
Actual or setpoint inputs (master current)
Use jumper and C0034 to change range
Output frequency
Motor current
Internal, stabilised DC voltage supply for
setpoint potentiometer
l
Level
(Lenze setting: in bolt print)
0 ... +5 V
0 ... +10 V
−10 V ... +10 V
0 ... +20 mA
+4 ... +20 mA
+4 ... +20 mA (open−circuit
monitored)
Level
(Lenze setting: in bolt print)
Voltage output:
0 ... +6 V
1)
0 ... +10 V
Current output:
(0 ... +12 mA)
1)
0 ... +20 mA
1)
+4 ... +20 mA
+5.2 V
EDK82ZAFAC−010 DE/EN/FR 5.0

Quicklinks ausblenden:

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis