8 Technical data
8.1 Display elements
Display
LEDs
8.2 Materials
TAPCON® 230
Front
Tray/rear
Housing (optional)
8.3 Dimensions
TAPCON® 230
W x H x D
TAPCON® 230 with housing
(optional) W x H x D
8.4 Power supply
Permissible voltage range
Max. nominal power consumption
Permissible frequency range
Overvoltage category
Surge test voltage
Internal fuse
Table 8: Power supply
5" TFT colour display
3 LEDs for operation display and messages
POWER, AVR STATUS, ALARM
RAISE, LOWER, AUTO, MANUAL, REMOTE
Aluminum, plastic
Stainless steel
Plastic
218 mm x 324 mm x 130 mm (8.58 in x 12.76 in x 5.12 in)
(without mating connector)
Mating connector 20 mm (0.79 in)
Overall: 500 mm x 500 mm x 300 mm (19.69 in x 19.69 in x
11.81 in)
Height with wall bracket: 521.3 mm (20.52 in)
85 to 265 V AC / V DC
U
: 100...240 V AC
N
U
: 100...240 V DC
N
25 W
50/60 Hz
OC III
5 kV, 1.2 µs/50 µs (IEC 60255-27)
250 V AC, 1.25 A, 5 x 20 mm, T characteristic
(slow acting), breaking capacity H (min.
1,500 A), operating temperature -30°C...
+100°C)
7820658/06 EN Technical data  