Commissioning
5 Commissioning
5.1 Device description file
The XML file contains all information on the measuring system-specific parameters
and the operating modes of the measuring system. The XML file is integrated by the
EtherCAT network configuration tool, in order to enable correct configuration and
commissioning of the measuring system.
The XML file is called "TR-Ethercat_Linear 30M_xxx.xml".
Download:
5.2 Bus status display
The EtherCAT measuring system is equipped with three diagnostic LEDs.
Figure 9: EtherCAT diagnostic LEDs
5.2.1 Indicator states and flash rates
LED
ON
OFF
Flickering
Blinking
Single flash
Double flash
Triple flash
Table 5: LED indicator states
TR-Electronic GmbH 2013, All Rights Reserved
Page 92 of 128
www.tr-electronic.de/f/TR-ELA-ID-MUL-0022
Description
constantly ON
constantly OFF
Equal ON and OFF times with a frequency of 10 Hz:
ON = 50 ms, OFF = 50 ms.
Equal ON and OFF times with a frequency of 2.5 Hz:
ON = 200 ms, OFF = 200 ms.
One short flash, 200 ms ON,
followed by a long OFF phase, 1000 ms.
A sequence of two short flashes, 200 ms ON/OFF,
followed by a long OFF phase, 1000 ms.
A sequence of three short flashes, 200 ms ON/OFF,
followed by a long OFF phase, 1000 ms.