1.
Insert the power supply wires through the cable gland (A).
2.
Shorten the connection wires to the appropriate length (avoid leaving
too much cable margin). The protective conductor PE must be longer
than the other conductors.
3.
Connect the cables to the J1 'push-lock' terminals without using
tools (4).
4.
Connect line (L) and neutral (N) as indicated in the chart.
We advise using flexible cables with a maximum section of 6 mm
5.
Connect the earthing wire to the J3 'Faston' terminal (2).
We recommend using FEMALE 6.3 x 0.8 'Fastons', better if with
restraint.
Incorrect installation may cause danger such as serious injury
or death.
Free2Move eSolutions S.p.A. does not assume any liability for damage
caused by non-compliant installation of the device. The qualified
personnel are responsible for the technical, state of the art
completion of the installation respecting the regulations in force.