SAFETY

2.1.

Intended purpose of easyWallbox

easyWallbox
and used for recharging electric vehicles in areas with restricted access, both in
inside and outside spaces (e.g. private homes, and private car parks or similar)
in compliance with the indications of Chapter 4 and local regulations.
The device can be used exclusively to charge full-electric or hybrid
vehicles compatible with Type 2 connectors, as in IEC 62196-2; it is not
compliant with other vehicles or devices. Some countries apply regulations that
require supplementary protection from the risk of electrocution. In any case,
the instructions for use in the manual and any additional documentation must
be read before using easyWallbox.
electricity network protected by a Residual Current Device (RCD, a differential
protection device) and a Miniature Circuit Breaker (MCB, an overcurrent
protection).
RCD
The system must include an adequate, specific differential switch. An RCD
of at least type A must be used as
the fault current DC of ≥ 6 mA through the use of a Residual Current
Monitor (RCM) with maximum nominal primary current of 80A.
The RCD must have a residual nominal operating current of not more than
30 mA, be of at least type A and comply with one of the following standards:
IEC 61008-1, IEC 61009-1, IEC 60947-2 and IEC 62423.
The RCD must disconnect all the live conductors. The over current protection
devices must comply with IEC 60947-2, IEC 60947-6-2, IEC 61009-1 or the
pertinent parts of the IEC 60898 series or IEC 60269 series.
easyWallbox
An insulation monitoring device (IMD) conforming to CEI EN 61557-8 must be
included for circuits in IT systems intended to charge electric vehicles, e.g.
through an isolating transformer or a battery system. A circuit powering a
connection point must not be included in a PEN conductor in a TN system.
is intended exclusively for fixed mounting. It can be installed
can be connected to type TT, TN and IT earthing systems.
easyWallbox
must be connected to an
easyWallbox
has internal monitoring of