Commissioning

EN
6.2.3 External Wiring
EN
DANGER! Explosion hazard due to incorrect mounting/installation!
EN
Non-compliance may result in serious or even fatal injuries.
EN
 Make sure that the cable diameter of the connection cables matches the nominal
EN
 Observe tightening torques.
EN
 Observe the insulating capacity and separation distances between intrinsically safe
EN
 Only use stopping plugs that have an EC type-examination certificate or
EN
EN
 Tighten the hexagon nuts of the cable entries with the tightening torques firmly so
EN
EN
 Install the connection lines in such a way that the permissible minimum bending
EN
EN
EN
 Make sure that there is sufficient equipotential bonding between the grounding
EN
 Tighten the cover of the enclosure with a tightening torque of 4.5 Nm.
EN
EN
Tightening torque
EN
• Connection thread: 2.3 Nm
• Cap nut: 1.5 Nm
EN
• Strain relief (for HSK-K-MZ): 3.5 Nm
EN
EN
7
Commissioning
EN
Before commissioning, carry out the following checks:
EN
 Check the enclosure for damage.
 Check that the mounting and installation have been performed correctly.
EN
When doing so, check whether all coverings and partitions for live components have been
EN
installed and fastened.
 Make sure that all openings/drilled holes in the enclosure are sealed with permissible
components. Dust and transport protection (adhesive tape or plastic caps) fitted at the
factory must be replaced with certified components.
 Make sure that the seals and sealing systems are clean and undamaged.
 Remove any foreign objects.
 If necessary, clean the connection chamber.
 Monitor whether the cables have been inserted correctly.
 Monitor whether all screws and nuts have been tightened firmly.
 Monitor whether all cable entries and stopping plugs have been tightened firmly.
 Monitor whether all conductors have been clamped firmly.
 Check whether all the specified tightening torques have been observed.
12
Grounding monitoring device
Type 8146/5075, Type 8146/5-V73,
Type 8150/5-V75
diameter of the cable entry.
and non-intrinsically safe circuits according to IEC/EN 60079-14.
an IECEx Certificate of Conformity to seal unused cable entries and drilled holes.
that the tightness of the enclosure and the strain relief protection at the connection
points are guaranteed.
radii values are not undershot for the respective conductor cross-section and
in a way that prevents mechanical damage to the conductor insulation from
sharp-edged or movable metal parts during installation.
monitoring device and the loading platform.
137208 / 8146624300