Installation

2.1

Electric connection

!
Warning
The appropriate regulations must be observed for the
electrical installation, in particular the following for
potentially explosive atmospheres:
-
-
-
Check that the power supply delivered by the coupler
agrees with the value specified on the rating plate of the
SITRANS P.
If the intrinsically-safe version has been operated with a
voltage of more than 15 V by mistake, the device may no
longer be used in intrinsically-safe applications.
The transmitter is powered from the bus coupler or link via the PROFIBUS-
PA. The bus coupler or link must obtain its supply from a source with a safety
extra-low voltage.
.
Note !
The following applies to routing of the bus cable:
-
-
-
-
SITRANS P
C79000-B5674-C207-1
The regulation concerning electric plant in potentially
explosive atmospheres (ElexV)
The specifications for the installation of electric plant in
potentially explosive atmospheres (DIN VDE 0165) and
The conformity certificate.
Route cable separate from cables with voltages > 60 V.
Avoid vicinity of large electric plant.
Only use recommended cable types.
The specifications only apply to correct installations.