Installation
7
UL-gerechte Installation
7.8
UL-gerechte Installation
7.8.1
Field wiring power terminals
7.8.2
Short-circuit current rating
7.8.3
Branch circuit protection
®
MOVIDRIVE
MDR60A..
52
Produkthandbuch – MOVI-C
HINWEIS
Folgendes Kapitel wird unabhängig von der Sprache dieser Dokumentation aufgrund
von UL-Anforderungen immer in englischer Sprache abgedruckt.
®
•
MOVIDRIVE
MDR60A..: - Only use copper cables with a rated thermal value of
60/75 °C.
•
Tighten terminals with the following permitted tightening torques:
Series
Size
®
MOVIDRIVE
2
MDR60A..
•
Suitable for the use in current circuits with a maximum symmetrical short-circuit
current of 200 kA:
®
– MOVIDRIVE
MDR60A.. if the devices are installed with the corresponding
®
MOVIDRIVE
drive inverter.
Max. voltage is limited to 500 V.
Integral semiconductor short-circuit protection does not replace the branch circuit fu-
sing. Branch circuit protection must be provided in accordance with the National Elec-
trical Code and any additional local codes.
The tables below list the permitted maximum fusing.
®
MOVIDRIVE
Max. line short circuit
MDR60A..
current
0150
AC 200 kA
®
1) If the MOVIDRIVE
MDR60A.. regenerative power supply unit is installed with the corresponding
®
MOVIDRIVE
drive inverter.
®
mit Netzrückspeisung MDR60A0150-503-00
in-lbs
16
Max. line voltage
1)
AC 500 V
Nm
1.8
Max. fuse rating
AC 50 A / 600 V