Troubleshooting
9
Troubleshooting
Display Status
If the keyboard is remote, it is possible to read the unit statuses also from
the display on the main board.
DSP1
DSP2
MENU DOWN UP
OK
Fig. 108
Standby: unit address (88 to the left) + online number
(88 to the right) On: frequency defrosting: dFdF
0.xx
1.xx
2.xx
3.xx
4.xx
Mode (8: Off; 0: Standby; 1: Cooling; 2: Heating, 4: hot water)
5.xx
6.xx
7.xx
T3: coil temperature
8.xx
T4: outside temperature
9.xx
T5: DHW temperature
10.xx
Taf1: Water side pipeline antifreeze
11.xx
Taf2: exchanger outlet temperature, antifreeze protection
12.xx
Tw: common outlet water temperature, after the last unit
13.xx
14.xx
15.xx
Tz total outlet water
16.xx
17.xx
Discharge temperature 1 (Tp1)
18.xx
Discharge temperature 2 (Tp2)
19.xx
Compressor 1 driver heat sink temperature
20.xx
Compressor 2 driver heat sink temperature
21.xx
Saturated discharge temperature
22.xx
Compressor current A
23.xx
Compressor current B
24.xx
25.xx
Electronic expansion valve opening A (actual valve/20)
26.xx
Electronic expansion valve opening B (actual valve/20)
27.xx
Electronic expansion valve opening C (actual valve/4)
28.xx
High pressure (heating mode) HP
29.xx
Low pressure (cooling mode) LP
30.xx
Suction superheat Tssh
31.xx
Suction temperature TH
32.xx
33.xx
34.xx
DC voltage A (reserved)
35.xx
DC voltage B (reserved)
68
Main board - back side
ON
ON
ENC4
S5
S12
NET_ADDRESS
0010045007-001
Unit address
Capacity
Number of units
T4 correction
Fan speed 1
Fan speed 2
Two inlet water
Two outlet water
THeatR recovery
---
Silent
Static pressure
Standby: unit address (88 to the left) + online number
(88 to the right) On: frequency defrosting: dFdF
Frequency limit reason (BIT0: T4 frequency limit;
BIT1: discharge temperature limit frequency;
BIT2: Total cooling output frequency limiter;
BIT3: Module temperature limit frequency;
BIT4: Limit frequency of cooling outlet water temperature;
BIT5: Heating high pressure frequency limiting;
36.xx
BIT6: Current limiting frequency;
BIT7: Voltage limit frequency;
BIT8: DC bus current limit;
BIT9: Refrigeration low pressure frequency limit;
BIT10: Limit frequency of heating water temperature;
BIT11: Reduced frequency of heating exhaust superheat;
BIT12: Power curtailment, not mode 1)
Defrosting process status (the first digit: T4 selection plan;
the second digit: the interval in the plan;
37.xx
the third and fourth digits together represent the
defrosting timing)
38.xx
EPROM error: 1: Error; 0: No error
39.xx
40.xx
Tc: Saturation temperature corresponding to high pressure in
41.xx
Te: Saturation temperature corresponding to low pressure in
42.xx
43.xx
T6a: eco exchanger inlet temperature
44.xx
T6b: eco exchanger outlet temperature
45.xx
46.xx
47.xx
Table 51
Alarm reset: turn the unit OFF and ON again.
Before resetting an alarm, identify and remove the cause that it is
generating the error. Repeated resets can cause irreversible damage.
Master unit
If the power supply of the Master unit is disconnected, all the units of the
group stop.
The unit is protected under the following conditions:
• High pressure or protection due to drain temperature;
• Low voltage;
• Compressor current protection;
• Frequency protection of the inverter compressor;
• Condenser high temperature;
• High temperature difference between the input and output water;
• Antifreeze protection;
• Drain temperature sensor malfunction;
• Low evaporator temperature;
• Frequency protection by voltage;
• Compressor inverter malfunction;
• Fan motor protection;
• Water return high temperature, in cooling;
• Low pressure antifreeze protection;
• High temperature of inverter compressor module.
When the unit fails or is in protection, the water pump continues working
(except for water flow alarm, voltage protection, phase sequence
protection).
Defrosting
Initial frequency
heating mode
cooling mode
Software version
Last error
---
CS3000 AWP – 6721852570 (2022/11)