MOUNTING INSTRUCTIONS
5
Mounting
en
14
M O U N T I N G I N S T R U C T I O N S | deTem2 Core A/P, deTem4 Core A/P
Position
LED color
Blue
3
Mount the active and passive units on a level surface.
b
Align the active and passive units at right angles to each other. The optical lens
b
systems must be located opposite one another.
In the case of the passive unit for small scanning ranges: Mount the active
°
and passive units at the same height, see dimensional drawings
With passive unit for long scanning ranges: Mount the passive unit offset
°
from the active unit. Be sure to observe a space of A = 71.8 mm, see
dimensional drawings
90˚
90˚
When using a QuickFix, FlexFix or Compact FlexFix bracket: For minor adjustments
b
when aligning, the active and passive units can be adjusted longitudinally in the
brackets.
For minor adjustments when aligning, the active and passive units can be
°
adjusted longitudinally in the brackets.
Position the brackets near the ends of the housing. If the device is exposed to
°
strong vibrations during operation, mount the top bracket at a height where
the offset in the multiple light beam safety device housing rests on the
bracket.
Observe the specified tightening torques. Higher torques can damage the bracket,
b
while lower torques are not secure enough to prevent the active and passive unit
from moving.
Make sure that the active and passive units are aligned correctly. The optical lens
b
systems of the active and passive units must be located opposite one another.
If necessary, use a spirit level to check that the components are parallel.
b
Dimensional drawing:
B
Dimensions based on the number of beams, active unit
Number of beams
2
4
Dimensional drawing:
C
Display
Diagnostics
B
and
D
.
A
Beam separation, dimension
S in mm
500
300
Labeling
1, 2, 3, 4, 5, 6, 7, 8
B
and
C
Length, dimension L in mm
672
1072
8024797/1GWI/2022-11-09 | SICK
Subject to change without notice
.