Herunterladen Inhalt Inhalt Diese Seite drucken

Models Gdm-Rc-100 And Gds-Rc-Hv - WIKA ACS-10 Betriebsanleitung

Kalibriersystem für gasdichteinstrumentierung
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 95
5. Commissioning, operation

5.8.2 Models GDM-RC-100 and GDS-RC-HV

For the models GDM-RC-100 and GDS-RC-HV there is a 12-pin terminal to plug into.
The pin assignment in the depressurised state is always as follows:
Wiring scheme
12 13 11 21 23 22 32 33 31 41 43 42
Terminal
EN
Status of switching output: Not pressurised
The switching functions can be found on the product label on the instrument or in the
order details.
Example:
For falling/rising breaking contacts, the configuration is as follows:
S1 = 0.61 MPa @ 20 °C, falling → Connect 1B to pin 13 and 1A to pin 11
S2 = 0.55 MPa @ 20 °C, falling → Connect 2B to pin 23 and 2A to pin 21
S3 = 0.55 MPa @ 20 °C, falling → Connect 3B to pin 33 and 3A to pin 31
S4 = 0.67 MPa @ 20 °C, rising → Connect 4B to pin 42 and 4A to pin 41
For falling/rising closing contacts, the configuration would be as follows:
S1 = 0.61 MPa @ 20 °C, falling → Connect 1B to pin 12 and 1A to pin 11
S2 = 0.55 MPa @ 20 °C, falling → Connect 2B to pin 22 and 2A to pin 21
S3 = 0.55 MPa @ 20 °C, falling → Connect 3B to pin 32 and 3A to pin 31
S4 = 0.67 MPa @ 20 °C, rising → Connect 4B to pin 43 and 4A to pin 41
78
S1
Gas Density Monitor GDM-RC-100
12...250 V AC (50...60Hz) / DC
max. 5 A @ 250 V AC / 30 V DC
max. 0.25 A @ 250 V DC
S2
S3
WIKA Betriebsanleitung Kalibriersystem, Typ ACS-10
S4

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis