Herunterladen Inhalt Inhalt Diese Seite drucken

Hitachi PC-ARFP1E Installations- Und Betriebshandbuch Seite 16

Vorschau ausblenden Andere Handbücher für PC-ARFP1E:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen
  • DE

Verfügbare Sprachen

  • DEUTSCH, seite 93
FUNCTION SELECTION AND SETTING

Table A Optional Setting Items for Function Selection
Items
Optional Function
Cancellation of heating temperature
b1
compensation due to uneven heat load
b2
Circulator function at heating Thermo-OFF
Enforced 3 Minutes minimum operation
b3
time of compressor
b4
Change of filter cleaning time
b5
Fixing of operation mode
b6
Fixing of setting temperature
Fixing of operation as exclusive cooling
b7
unit
b8
Automatic COOL/HEAT operation
b9
Fixing of fan speed
bA
Not prepared
Cooling temperature compensation due to
bb
uneven heat load
bC
Not prepared
bd
Not prepared
bE
Not prepared
C1
Not prepared
C2
Not prepared
C3
HA function (only for Japanese market)
C4
Drain Pump Operation at Heating
Hi speed
C5
(Except for Hi Speed at Heating Thermo-
OFF)
C6
Hi speed at heating Thermo-OFF
Canceling of enforced 3 minutes minimum
C7
operation time of compressor
C8
Thermistor of remote control switch
C9
Not prepared
CA
Not prepared
Cb
Selection of forced stoppage logic
CC
Not prepared
Cd
Not prepared
CE
Not prepared
CF
Change of louver swing angle
8
PMML0404A rev.1.1 - 06/2022
Individual setting Setting condition
00
01
02
00
01
00
01
00
01
02
03
04
00
×
01
00
×
01
00
×
01
00
×
01
00
×
01
×
-
00
×
01
02
-
-
-
-
-
-
-
-
-
-
00
01
00
01
00
01
02
00
01
00
01
00
01
02
-
-
-
-
00
×
01
×
-
-
-
-
-
00
01
02
Contents
Standard +4ºC
Removal (offset elimination)
Set temperature +2
C (*1)
o
Not available
Available
Not available
Available
Standard
100 hrs
1,200 hrs
2,500 hrs
No indication
Standard
Fixed
Standard
Fixed
Standard
Fixed
Not available
Available
Standard
Fixed
Not used
Standard (No Compensation)
Set Temp. –1
C
o
Set Temp. –2
C
o
Not used (Use as 00 conditions)
Not used (Use as 00 conditions)
Not used (Use as 00 conditions)
Not used (Use as 00 conditions)
Not used
Not available (Use as 00 conditions)
Available
Not available
Available
Not available
Hi Speed 1
(*2)
Hi Speed 2
Not available
Available
Standard
Cancellation
Not available
Control by thermistor of remote control switch
Control by average value of indoor suction
thermistor and thermistor of remote control switch
Not used
Not used
Forced stoppage input: A Contact
Forced stoppage input: B Contact
Not used (Use as 00 conditions)
Not used (Use as 00 conditions)
Not used (Use as 00 conditions)
Standard (7-Step Operation)
Cold draft prevention (5 Steps: lower 2 steps cut off)
High ceiling (5 Steps: upper 2 steps cut off)

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis