3.1
Structure of the MENU tree of the REC10CH
MENU
SETTINGS
TIME & DATE
DAYLIGHT SAVINGS TIME
LANGUAGE
BACKLIGHT
TIME SCHEDULE
MAIN
ZONE 1
ZONE 2
DHW
HP DHW
TECHNICAL
INSTALLATION
ZONES MANAGER
MODIFY ZONE
ACTUATION TYPE
REQUEST TYPE
BE16 ADDRESS
HYDRAULIC CONF
ZONE TYPE
MIN CH SET
MAX CH SET
CHANGE NAME
PI - PROPORTIONAL
PI - INTEGRAL
VALVE RUN
CLOSING AT POWER ON
OUTLET OVER
OUTLET OVER TEST TIME
OUTLET OVER WAIT TIME
OUTLET OVER REST TIME
FREEZE PROT TEMP
FREEZE PROT OFFSET
FREEZE PROT T EXT
POR
ADD ZONE
DELETE ZONE
SENSOR CALIBRATION
SYSTEM RESET
PARAMETERS
ANTI-CYCLE FUNCTION
HYST ON HIGH TEMP
HYST OFF HIGH TEMP
HYST ON LOW TEMP
HYST OFF LOW TEMP
SP INCR HIGH TEMP
DEFAULT VALUE FACTORY
SET
FUNCTION ACTIVE
FUNCTION NOT ACTIVE
5 min
MAIN
ITRF05/boiler card
ITRF05/boiler card
THERMOSTAT / TEMPERATURE PROBE / REC10CH
THERMOSTAT
--
DIRECT ZONE
DIRECT ZONE
HIGH TEMP (HT)
HIGH TEMP (HT)
20°C (HT)
20°C (LT)
80.5°C (HT)
MIN CH SET
45°C (LT)
5
10
120 sec
140 sec
55°C
0 min
2 min
VALVE RUN
2 min
6°C
5°C
10°C
0 (1 if REC10 in the AMBIENT)
0.0°C
3 min
5°C
5°C
3°C
3°C
5°C (0°C if instantaneous boiler)
MINIMUM
MAXIMUM
VALUE
VALUE
FUNCTION ACTIVE
ENGLISH / ITALIANO / ...
1 min
15 min
MAIN / ZONE 1 / ZONE 2
BE16
MASTER / REC10CH SLAVE
1
6
MIXING ZONE
LOW TEMP (LT)
20°C
MAX CH SET
80.5°C (HT)
45°C (LT)
0
99
0
99
0 sec
120 sec
0 sec
240 sec
0°C
100°C
0 min
240 min
240 min
0 min
240 min
-10°C
50°C
1°C
20°C
0°C
100°C
0
1
- 6.0°C
6.0°C
0 min
20 min
2°C
10°C
2°C
10°C
2°C
10°C
2°C
10°C
0°C
10°C
ENGLISH
EN
ACCESS LEVEL
SET
NOTES
VALUE
USER
USER
USER
USER
USER
USER
USER: only if POR = 1
USER: only if POR = 1 and zone
added
USER: only if POR = 1 and zone
added
USER: only if PLANT
CONFIGURATION = WATER TANK
USER: only if HP present and
USE FOR DHW active
INSTALLER
INSTALLER
INSTALLER
INSTALLER
INSTALLER: only MAIN zone
INSTALLER
INSTALLER: only zones with
ACTUATION=BE16
INSTALLER: only zones with
ACTUATION=BE16
INSTALLER
INSTALLER
INSTALLER
INSTALLER
SERVICE: only mixing zones with
ACTUATION=BE16
SERVICE: only mixing zones with
ACTUATION=BE16
SERVICE: only mixing zones with
ACTUATION=BE16
SERVICE: only mixing zones with
ACTUATION=BE16
SERVICE: only LT zones with
ACTUATION=BE16
SERVICE: only LT zones with
ACTUATION=BE16
SERVICE: only LT zones with
ACTUATION=BE16
SERVICE: only LT zones with
ACTUATION=BE16
SERVICE: only zones with
ACTUATION=BE16
SERVICE: only zones with
ACTUATION=BE16
SERVICE: only zones with
ACTUATION=BE16
INSTALLER
INSTALLER
INSTALLER
INSTALLER
INSTALLER
INSTALLER
INSTALLER
SERVICE
SERVICE
SERVICE
SERVICE
SERVICE
9