EVACUATING

Air Purge

This air conditioner can be installed up to the connecting pipe length and height difference in the following table.
Max. connecting
Capacity rank
pipe length (m)
SM110, SM140 type
With respect to the preservation of terrestrial environment, adopt "Vacuum pump" for air purge (Evacuate air in
the connecting pipes) when installing the unit.
• Do not discharge the refrigerant gas to the atmosphere to preserve the terrestrial environment.
• Use a vacuum pump to discharge the air (nitrogen, etc.) remained in the set. If the air remains, the capacity
may decrease.
For the vacuum pump, be sure to use one with backflow preventer so that the oil in the pump does not backflow
into the pipe of the air conditioner when the pump stops. (If oil in the vacuum pump is put in an air conditioner
including R410A, it may cause trouble on the refrigeration cycle.)

Vacuum pump

As shown in the figure, connect the charge hose after the manifold valve are closed completely.
Attach the connecting port of the charge hose with a projection to push the valve core (setting pin) to the charge port of the set.
Loosen the flare nut of the packed valve (Gas side) a little to check the air passes through. (*2)
Execute vacuuming until the compound pressure gauge indicates –101kPa (–76cmHg). (*1)
Leave the vacuum pump as it is for 1 or 2 minutes, and check the indicator of the compound pressure gauge does not return.
Open fully the valve stem or the valve handle. (First, at liquid side, then gas side)
All manuals and user guides at all-guides.com
Outdoor unit at upper side
50
30
Open handle Low fully.
Turn ON the vacuum pump (*1)
Tighten the flare nut again.
Close handle Low completely.
Turn OFF the vacuum pump.
Disconnect the charge hose from the charge port.
Tighten valve and caps of the charge port surely.
9
Height difference (m)
Outdoor unit at lower side
30
Hexagonal
wrench size
4 mm