Herunterladen Inhalt Inhalt Diese Seite drucken

Technical Data; Classification To Din En 50155; Ul-Data; Ccc-Data - Dold VARIMETER IMD RN 5897/020 Betriebsanleitung

Isolationswächter
Vorschau ausblenden Andere Handbücher für VARIMETER IMD RN 5897/020:
Inhaltsverzeichnis

Werbung

Verfügbare Sprachen

Verfügbare Sprachen

Technical Data

Wire connection
Cross section:
Stripping length:
Wire fixing:
Fixing torque:
Mounting:
Weight:
Dimensions
Width x height x depth:

Classification to DIN EN 50155

Vibration and
shock resistance:
Ambient temperature:
Protective coating of the PCB: No

UL-Data

Meas. ciruit L1(+)/L2(-) to PE1/PE2 (with coupling device RL / RP 5898)
Max. voltage range U
:
N
Output voltage at
L(+)/L(-), VSG1/VSG2:
Switching capacity:
Wire connection:
Test specification:
Technical data that is not stated in the UL-Data, can be found
in the technical data section.
nfo

CCC-Data

Switching capacity
To AC 15
NO contact:
NC contact:
Technical data that is not stated in the CCC-Data, can be found
in the technical data section.
nfo

Variants

RN 5897.12/020:
DIN 46228-1/-2/-3/-4
0.5 ... 4 mm² (AWG 20 - 10) solid or
0.5 ... 4 mm² (AWG 20 - 10)
stranded wire without ferrules
0.5 ... 2.5 mm² (AWG 20 - 10)
stranded wire with ferrules
6.5 mm
Cross-head screw / M3 box terminals
0.5 Nm
DIN rail
IEC/EN 60715
Approx. 205 g
52.2 x 90 x 71 mm
Category 1, Class B
IEC/EN 61373
OT1 compliant
RL 5898
RP 5898
AC 0 ... 400 V
AC 0 ... 600 V
DC 0 ... 500 V
DC 0 ... 600 V
Max. AC / DC 230 V
Pilot duty C300, R300
5A 250Vac
2A 30Vdc
60 °C / 75 °C copper conductors only
Torque 0.5 Nm
ANSI/UL 60947-1, 5
Edition
th
ANSI/UL 60947-5-1, 3
Edition
rd
CAN/CSA-C22.2 No. 60947-1-13,
2
Edition
nd
CAN/CSA-C22.2 No. 60947-5-1-14,
1
Edition
st
3 A / AC 230 V
1 A / AC 230 V
With modified alarm value range
Alarm ("R
"):
A
kΩ: 10, 20, 30, 50, 100, 200, 300, 500
Article number: 0069226

Standard Types

RN 5897.12/020/61
Article number:
• Auxiliary voltage:
RN 5897.12/020/61
Article number:
• Auxiliary voltage:
RN 5897.12/020/61
Article number:
• Auxiliary voltage:
• Outputs:
• Setting range pre-warning:
• Setting range alarm:
• With connection facility of a coupling device RL 5898 or RP 5898
• Max. line capacitance:
• Energized or de-energized on trip
• Selection of type of network
• Width:

Ordering Example for Variants

RN 5897 .12 /020 /61 AC/DC 24 ... 60 V 1 kΩ - 100 kΩ 20 kΩ - 500 MΩ

Accessories

RL 5898/61
Article number: 0068315
• Coupling device for RN 5897.12/020
• Extension of nominal voltage range U
to DC 500 V, AC 400 V
• Weight:
• Dimensions
- Width x height x depth:
35 x 90 x 71 mm
Insulation monitor
connection
Measuring ciruit
M12054_a
26
DC 12 ... 24 V
0068260
DC 12 ... 24 V
AC/DC 24 ... 60 V
0068258
AC/DC 24 ... 60 V
AC/DC 85 ... 230 V
0068259
AC/DC 85 ... 230 V
1 changeover contact for pre-warning
1 changeover contact for alarm
20 kΩ ... 500 kΩ
1 kΩ ... 100 kΩ
5 µF
52.5 mm
Setting range Pre-warning
Setting range alarm
Auxiliary voltage
UL approval
Variant, if required
Contacts
Type
N
Approx. 60 g
RN 5897/020 / 01.03.22 en / 518A

Werbung

Inhaltsverzeichnis
loading

Inhaltsverzeichnis