4.4
Approvals, conformities, certifications
The product is TÜV-tested (report number 968/FSP 2170.01/21).
4.5
Technical data
Parameter
General specifications
Dimensions (W x H x D)
- Type: -1C
- Type: -2CM
- Type: -2CM Optimum
Connection burner
Connection tank
Nozzle throughput
Return flow
Separating capacity air/gas, depend-
ing on air content of fuel
Mounting position
Operating overpressure
Response pressure pressure relief
device
Suction pressure
Test pressure
Filter insert
Housing material
Ambient conditions
Ambient temperature operation
Temperature of the medium
Product description
Value
184 x 223 x 109 mm
184 x 253 x 109 mm
184 x 340 x 109 mm
3
2 x G
male with 60° cone for
/
8
burner hose
3
G
female at shut-off valve
/
8
Max. 100 l/h
Max. 120 l/h
Max. 4 l/h (de-aeration unit only)
Max. 6 l/h (as per EN 12514-3)
Float housing vertical to the top
Max. 0.7 bar (corresponds to a
static liquid column of approxi-
mately 8 m)
1.5 ±0.5 bar
Max. -0.5 bar
6 bar
Sintered plastic or paper filter 
"Opticlean"
plastic, glass-fibre reinforced
0 ... 60 °C
0 ... 60 °C