Wood
Place the wood mounting across the roof
beam, then install the hanging screw bolts.
(See Fig.4.4)
Wood mounting
New concrete bricks
Inlay or embed the screw bolts. (See Fig. 4.5)
(Blade shape insertion)
Original concrete bricks
Use an embedding screw bolt, crock, and
stick harness. (See Fig.4.6)
(Pipe hanging and embedding screw bolt)
Steel roof beam structure
Install and use the supporting steel angle.
(See Fig.4.7)
Hanging
bolts
CAUTION
The unit body must be completely aligned with
the hole. Ensure that the unit and the hole are
the same size before moving on.
2. Install and fit pipes and wires after you have
finished installing the main body.When
choosing where to start, determine the
direction of the pipes to be drawn out.
Especially in cases where there is a ceiling
involved, align the refrigerant pipes, drain
pipes, and indoor and outdoor lines with their
connection points before mounting the unit.
Page 10
Page 10
Roof beam
Ceiling
Hanging screw bolts
(Slide insertion)
Steel bar
Embedding screw bolt
Hanging screw bolt
Supporting
angle steel
3. Install hanging screw bolts.
Cut off the roof beam.
Strengthen the point at which the cut was
made. Consolidate the roof beam.
4. After you select an installation location,align
the refrigerant pipes, drain pipes, as well as
indoor and outdoor wires with their
connection points before mounting the unit.
5. Drill 4 holes 10cm (4") deep at the ceiling
hook positions in the internal ceiling. Be sure
Fig. 4.4
to hold the drill at a 90° angle to the ceiling.
6. Secure the bolt using the washers and nuts
provided.
7. Install the four suspension bolts.
8. Mount the indoor unit with at least two
people to lift and secure it. Insert suspension
bolts into the unit's hanging holes. Fasten
Fig. 4.5
them using the washers and nuts provided.
(See Fig. 4.8).
Fig. 4.6
9. Mount the indoor unit onto the hanging
screw bolts with a block. Position the indoor
Fig. 4.7
unit flat using a level indicator to prevent
leaks. (See Fig. 4.9).
Shockproof cushion
Hanging screw bolt
NOTE: Confirm the minimum drain tilt is 1/100
or more.
Fig. 4.8
Screw nut
Overhang part
Washer